|
Safety
and Buildings
Division
Energy Conservation Code Council Meeting Summaries
Meeting summaries are subject
to review at
subsequent meetings
Wednesday, October 28, 2009, 9 a.m.to 3 p.m.,
City of Madison Fire Station #11, 4011 Morgan Way, Madison, Wisconsin
Council Member Attendance: Jeffrey Boldt (alt. Paul Hansen) -
P; Thomas Cox - A; Dan Dehnert - P; Ross DePaola - P; Dan Hanson - Ex;
Michael Mamayek - P; Dave Osborne - P; Gerald Schulz - A; Harry Sulzer
- P
Commerce Staff: John Spalding, Jim Smith, Randy Dahmen, Lori Ann
Curley
Welcome, introductions, housekeeping, review agenda and
previous meeting’s progress report
Ross DePaola thanked everyone for their time. The agenda was
approved as written. Any needed modifications to the progress
report of the October 6, 2009, meeting can be sent to Lori Ann
Curley.
Identify new requirements that the council wants to
recommend as Wisconsin-based modifications
Ross DePaola started the discussion with a brief overview of the
international codes. The council discussed the following:
- IECC 101.5.2: This section is poorly defined. The council
tabled this issue until a search for more information can be done on
conditioned space. The Council must address both heating, which
is covered by an old Wisconsin modification, and cooling, which may
need to be augmented.
- IECC 303.3: No action taken by the council.
- IECC 402.2.9: The council decided to remove the “Class
I” reference and include “minimum of one perm. or
less”
- IECC 402.2.8 & 502.2.6: No action taken by the council.
- IECC 403.6: IRC 1401.3 vs. ACCA Manual S: tabled for further
review.
- IECC 403.9.3 & 504.7.3: No action taken by the council, but
they recommend that this be taken up by the umbrella councils.
- IECC 405.2: The council voted to accept these changes.
- IECC Table 402.2 (1): The council voted to accept these changes.
- IECC Table 502.2 (1): Remove the NR reference in “Zone
6/Below
grade wall” box if not done in the final version of IECC 2009.
- IECC 503.2.4.4 & 502.4.5: Create a Wisconsin modification
creating an exception for no motorized damper in a commercial kitchen
Type I/grease reduction exhaust duct.
- IECC 503.2.5: No action taken by the council.
- IECC 503.2.5.1: No action taken by the council.
- IECC 503.2.6 & IECC 503.3.1: No action taken by the council.
- IECC Table 503.2.8: No action taken by the council.
- IECC 503.3.1/Comm 63.0503: No action taken by the council.
- IECC 503.4.5.3: No action taken by the council.
- IECC 503.4.5.4: No action taken by the council.
- IECC 505.6.2 Exception 5.: No action taken by the council.
- IECC Table 505.6.2: No action taken by the council.
Go over next steps, set next meeting if necessary, and adjourn
Another meeting can be arranged if needed. Questions may be
dirwected to Jim Smith, jim.smith@wisconsin.gov, 608-266-0251.
Tuesday, October 6, 2009, 9 a.m. to 3 p.m.,
City of Madison Fire Station #11, 4011 Morgan Way, Madison, Wisconsin
Council member attendance: Jeffrey Boldt (alt.:
Paul Hansen) P; Thomas Cox A; Dan Dehnert P; Ross DePaola P; Dan Hanson
P; Michael Mamayek P; Dave Osborne P; Gerald Schulz P; Harry Sulzer P
Commerce Staff: John Spalding, Jim Smith, Randy
Dahmen, Lori Ann Curley
Guests: Jim Boullion, Associated General
Contractors of Wisconsin; Doug Schorr, state Department of
Administration; David Soens, UW-Madison, Engineering Professional
Development;
Welcome, introductions, housekeeping and review agenda
Ross DePaola opened the meeting with introductions and thanking
everyone for their time. The agenda for the current meeting was
accepted as presented.
Review Council scope and purpose and previous
meeting’s progress report
Ross DePaola reviewed the Council’s purpose to review the changes
in
the 2009 Energy Code and the Wisconsin modifications to that code.
Gerald Schulz moved to accept the progress report of the August , 11,
2009, meeting, and Dave Osborne seconded. The motion passed.
Review Council member comments submitted in writing
- IECC 502.4.4 Hot Gas Bypass Limitation: Add this addition in the
Wisconsin code.
- IECC 503.2.10.1 Allowable fan floor horsepower: The Council will
check on design specifics, but otherwise this code is acceptable.
- IECC 503.3.1 Economizers: Keep Wisconsin Modification (Table 63.0503)
regarding Economizers e”54,000 Btu/h, but add “only for
packaged
rooftop units e” 33,000 Btu/h”; Eliminate Table 503.3.1 (1)
and its
footnote a.
- IECC 503.4.3.3.2.2 Climate Zones 5 through 8: Remove the words
“or closed”.
- IECC 503.4.3.4 Part load controls: The Council decided to keep this
until ASHRAE 90.1 addendum ak, which is currently a public hearing
draft, is approved.
- IECC 503.4.5 – exceptions 4: and 6. Hansen moved to remove
these, but no one seconded; motion failed.
- IECC 503.4.5.4 – exception 3: Hansen moved to remove this, and
Osborne seconded; motion failed.
- Comm 63.0102: See modifications below
- Comm 63.0402: Building thermal envelope: The Council proposed to
change the wording of this Wisconsin modification:
In addition to the requirements and the exceptions in IECC section 402:
(1) MOISTURE CONTROL. Except as specified in sub. (2), the building
design may not create conditions of accelerated deterioration from
moisture condensation. Above-grade frame walls, floors and ceilings
shall be provided with an approved vapor retarder. The vapor retarder
shall be installed on the warm-in-winter side of the thermal
insulation.
(2) EXCEPTION. Where other approved means to avoid condensation in
unventilated framed wall, floor, roof, ceiling cavities, and box sills
are provided.
Comm 63.502: Moisture control: The Council proposed to change the
wording of this Wisconsin modification:
In addition to the requirements and the exceptions in IECC section 502:
1) MOISTURE CONTROL. Except as specified in sub. (2), the building
design may not create conditions of accelerated deterioration from
moisture condensation. Above-grade frame walls, floors and ceilings
shall be provided with an approved vapor retarder. The vapor retarder
shall be installed on the warm-in-winter side of the thermal
insulation.
2) EXCEPTION. Where other approved means to avoid condensation in
unventilated framed wall, floor, roof, ceiling cavities, and box sills
are provided.
- Comm 63.0503 (5) (b) 1.: See discussion of Wisconsin-based
requirements below.
- Comm 63.0505 (1) (a): Eliminate the Wisconsin modification and use
the new IECC code.
- Comm 63.0506: Include the latest version of the approved
settings.
Working Lunch: During lunch, Jim Boullion of
the Associated General Contractors of Wisconsin gave the council a
presentation on the Green House Gas Task Force Recommendations and
asked the council for their input.
Revisit current Wisconsin-based requirements
- Comm 63.001 Purpose: Wisconsin Modification to remain.
- Comm 63.002 Application:
Keep subsection (1) and paragraph (2) (c) here or move to chapter
Comm 61.
Paragraphs (2) (a) and (b) may be eliminated.
- Comm 63.0100 Changes, additions or omissions to IECC: Staff will
renumber as necessary.
- Comm 63.0101 Administration and enforcement: Change reference to IECC
section 106 to section 109.
- Comm 63.0102 Materials, systems and equipment:
Subsection (1) is eliminated due to the repeal of Wisconsin Statute
section 101.124;
Move subsection (2) to 303.1.4 as additional information.
- Comm 63.0202 General definitions: Wisconsin Modification to remain.
- Comm 63.0302 Exterior design conditions: Wisconsin Modification to
remain.
- Comm 63.0401 Certificate: Wisconsin Modification to remain.
- Comm 63.0402 Building thermal envelope: See proposed changes above.
Eliminate IECC 402.4.2.
- Comm 63.0403 Systems:
Subsection (1) to remain.
Subsection (2) to be eliminated, but look up the IRC section
M1601.4.1 for testing information.
Subsection (3) to be eliminated.
- Comm 63.0404 Calculation software tools: Change the note to read:
Note: The federal Department of Energy has developed REScheckTM,
a computer program that may be used in demonstrating compliance for a
residential building which has no more than 3 stories above grade and
has 3 or more dwelling units. The latest version of the REScheck
program may be downloaded at http://www.energycodes.gov/. When using
the program, the applicable code must be defined as the “2009
IECC.”
The use of the “Wisconsin” option will apply requirements
associated
with a 1 or 2 family dwelling, which are more restrictive than those
associated with low-rise multifamily buildings.
- Comm 63.0501 General application: Staff will renumber as necessary.
- Comm 63.0502 Moisture control: Staff will renumber as necessary.
- Comm 63.0503 Building mechanical systems:
Subsection (1): Wisconsin Modification to remain.
Subsection (2): Wisconsin Modification to remain.
Subsection (3): Eliminate the tables.
Subsection (4): Eliminate the Wisconsin Modification.
Subsection (5): Eliminate the Wisconsin Modification.
Subsection (6): Eliminate the Wisconsin Modification.
Subsection (7): Wisconsin Modification to remain.
Subsection (8): See IECC 503.3.1 Economizers above.
Subsection (9): Wisconsin Modification to remain.
- Comm 63.0504 Service water heating: Wisconsin Modification to remain.
- Comm 63.0505 Lighting systems:
Subsection (1): Eliminate the Wisconsin Modification except move
paragraph (b) to section 505.2.2.3.
Subsection (2): Keep the Wisconsin Modification, but Department
of Commerce staff must double check the note/exception in IECC section
501.2, and eliminate subdivision (a) 3.
Subsection (3): Eliminate the Wisconsin Modification.
Subsection (4): Eliminate the Wisconsin Modification.
- Comm 63.0506 Total building performance: See proposed changes above.
- Comm 63.0900 Referenced standards: Staff will renumber as necessary..
Identify new requirements that the Council wants to recommend as
Wisconsin-based modifications - Tabled until the next meeting.
Finalize concepts and changes to the energy conservation code
requirements - Tabled until the next meeting.
Go over next steps, set next meeting if necessary, and adjourn
The next meeting is scheduled for Wednesday,
October 28, 2009, from 9 a.m. to 3: p.m., at the City of Madison Fire
Station #1, Madison Wisconsin.
If you have questions, contact Jim Smith,
jim.smith@wisconsin.gov, 608-266-0251.
Tuesday,
August 11, 2009, 9:30 a.m. to 2 p.m., City
of Madison Fire Station #11, 4011 Morgan Way, Madison,
Wisconsin.
Council Member Attendance: Paul Hansen (for Jeffrey Boldt)
- P; Thomas Cox - Ex; Dan Dehnert - P; Ross
DePaola - P; Dan Hanson - P; Michael Mamayek
- P; Dave Osborne - P; Gerald Schulz - P;
Harry Sulzer - P
Commerce Staff: Jim Smith, Randy Dahmen, Lori Ann
Curley
Welcome, introductions, housekeeping and review agenda
Jim Smith opened the meeting with introductions and thanking everyone
for their time. The agenda for the current meeting was
accepted as presented.
Review Council scope and purpose
Jim Smith stated the council’s purpose to review the changes
in the 2009 Energy Code and the Wisconsin modifications to that code.
Review previous meeting’s progress report
Gerald Schulz moved to accept the progress report of the February 26,
2007, meeting, and Dave Osborne seconded. The motion passed.
Elect Chairperson
Dave Osborne nominated Ross DePaola, and Gerald Schulz
seconded. The motion passed. The council determined
that a vice-chair was not needed.
Review text of the Wisconsin Commercial Building Code
Energy Conservation Advisory Council Workbook
Ross DePaola started the discussion with a brief overview of the
international codes. The Council discussed the following:
- 101.4.2: Historic Buildings: Additions, but not
maintenance, are subject to the new code.
- 101.4.3: Exceptions should be moved to Comm 61, but they
would not be in the Energy Code (Comm 63). The Department of
Commerce staff will clean up the locations of the code, especially the
administrative provisions (Comm 61).
- 101.5.2 (2): Conditioned spaces in multi-use buildings,
especially basement garages, are kept at approximately 45 degrees, but
first floor retail is kept at approximately 68 degrees, which can cause
problems.
- Part II of the I-Code will go to Comm 61: Administration and
Enforcement.
- 303.1.4: It was suggested the new reference would
only apply to home insulations because of the title of the reference
and language in the overview and that commercial insulations are to be
limited to those found in ASTM. It was explained that because
the code itself referenced that CFR and did not incorporate any such
limitation, it was likely intended to be accepted for all insulations,
whether installed on homes or commercial
buildings.
- 401.3: Certificate: Wisconsin does not require a
certificate, but Table 402.1.1 has requirements for R-value
certificate.
- 402.2.1: The modification (that one cannot use
the reduction for the new U-value approach) relating to ceilings with
attic spaces was discussed and included a conversation about how the
reduced R value (where it states R-30 is "deemed to satisfy" where R-38
is required and also that R-38 can be used where R-49 is required)
provisions that were not changed are applied. 402.4.2.1 and .2: Testing
option and Visual inspection
option: the council may recommend deleting reference to a code
official. Questions arose such as "How did one comply with
the code: test or visual?" "Is Wisconsin going to
require this?" "What cost will be added?" The
council needs to review this further.
- 403.1.1: Programmable
thermostat: Do we want to expand it to include boiler systems?
- 403.2.1.: Ducts: Wisconsin’s code requires flexible R-4
insulation.
- 403.2.2 1.: Is this
requirement viable? Does Wisconsin want to keep it? Would it require a
third-party test? There are issues of
square footage of floor space versus square footage of duct work.
-
403.8: Snow melt system
controls: Wisconsin has repealed the no heated sidewalk
statute if the system is controlled/energized within a commercial
building.
-
405.2: Add a note in the
building envelope and Addendum “G”
-
405.4.1: Compliance
software tools: Is it really used in residential building?
-
405.5.2: Have the
performance check computer programs been updated (it’s
optional)?
- Table 502.2(1): Climate
zone 6: is the information in the row “below grade
wall” accurate? Check the errata.
-
502.4.5: Outdoor air
intakes and exhaust opening: maybe remove the exception.
-
503.2.5.1: Demand
controlled ventilation: Consider the use of economizers.
503.2.11: Issue for the
new smoking ban.
503.3.1(1) footnote a. Does this make sense? A clarification may be
needed.
Review text of the Wisconsin modifications from the
Current Wisconsin Commercial Building Code, Chapter Comm 63
Jim Smith will condense the information and send it to the Council.
Assign homework
The council was instructed to re-review all the information and share
information with those they represent and get their feedback. Feedback
and any Wisconsin modifications that are being proposed are to
be provided in writing to Commerce staff by September 15, 2009.
Set next meeting and adjourn
The next meeting is scheduled for Tuesday, October 6, 2009, from 9:00
AM to 2:00 PM, at the City of Madison Fire Station #11 - Conference
Room.
Questions may be directed to Jim Smith,
jim.smith@wisconsin.gov, 608-266-0251.
Monday,
February 26,
2007, 9:30 a.m. to 1:30 p.m., Department
of
Commerce 201 W. Washington
Ave., Room 3C, Madison, Wisconsin
Council Member Attendance: Jeffrey
Boldt
- P; Dan Dehnert - P; Ross DePaola - P;
Kevin Lichtfuss - P; Dave Osborne - P; Gerald Schulz
- A; Harry Sulzer - P; Bob Wiedenhoefer - P.
Guests:
Norman Bair, state Department of Administration, Division of
Energy; Tim Semmann, Wisconsin Builders Association
Commerce
Staff: Jim Quast, Jim Smith, Bob
DuPont, Randy Dahmen, Diane Meredith.
1. Welcome and introductions
Jim
Quast opened the meeting with introductions. The progress
report from the previous meeting dated November 16, 2005 and the agenda
for the current meeting were accepted as presented.
2.
Division Updates
The Division received approximately 260
public hearing comments on the proposed changes to update the Wisconsin
Commercial Building Code (WCBC). The majority of the hearing
comments related to the requirement that sprinklers be installed in all
multifamily housing, and the remaining comments related to energy,
mechanical and building technical requirements. The
anticipated effective date of the revised WCBC is late summer or early
fall.
3. Discussion of Public Hearing
Comments/Responses
The hearing comments received relative to
the International Energy Conservation Code (IECC) and the WCBC were
distributed and the following discussions and recommendations were
offered:
IECC section 505.5.1.4: A
Wisconsin modification will be created to recognize the use of a
current limiting device similar to California Title 24 relative to
calculating the wattage loads for track lighting.
Comm
63.0505 (2) (b): The definition of “effective
aperture” will
be included under the code.
IECC section
505.2.2.1: It was suggested a Wisconsin modification be
developed to ensure the ASHRAE 90.1 standard has a similar requirement
for dual switching as required under the IECC. Under the
proposed public hearing draft section Comm 63.0501 (4), dual switching
is already required even if the ASHRAE method is followed.
Comm
630505: Additional lighting exceptions regarding the total
connecting lighting power will be included to reflect the proposed
changes for the 2009 edition of the IECC.
IECC
chapter 4: The suggestion to limit the amount of glazing or
window area restrictions will not be included since the federal
Department of Energy (DOE) study concluded the elimination of the
window restriction will not have a significant impact on energy
use.
IECC 63.0503 (7) (b) and Table
63.0503: The council members discussed the use of economizers
and whether a split-system should be considered a complex system as
opposed to a simple system as currently considered under the
IECC. A recommendation was made by the council to modify
Table 63.0503 to include split systems and groundwater source cooling
systems under the complex systems, which will require economizers on
cooling systems greater than 54,000 Btu/h regardless of the occupancy.
Comm
63.0506: The code currently recognizes the use of the
REScheck computer program for demonstrating that the building envelope
complies with the code; however, the use of COMcheck-EZ is not
recognized under IECC chapter 5. An informational note will
be added to the code under s. Comm 63.0506 to recognize the use of
COMcheck-EZ computer program.
IECC Table
503.2.8: A comment was received indicating the code fails to
define the temperatures at which steam, hot water, chilled water, brine
or refrigerant are to be recognized. It was decided the
temperatures could be determined through the specified exceptions and
standard dictionary definitions, so no code change will be necessary.
IECC
505.6: A comment suggested the current code clearly
identifies how compliance can be achieved for interior lighting, but
does not include the same language for exterior lighting. It
was recommended an amendment be included for exterior lighting for
enforcement purposes. However, it was noted the IECC
provisions and the ASHRAE provisions are basically the same and
compliance with IECC 505.6 can be achieved through interpretation of
terms used in the code, such as, “densities
permitted.”
The
council members discussed the topic of ventilation under the
International Mechanical Code (IMC), where the IMC typically requires
15-20 cfm/person of outside air for ventilation and recognizes natural
ventilation for all occupancies, as compared to the WCBC requiring 7.5
cfm/person, and mechanical ventilation for most occupancies. The
following comments and concerns were raised during the
council’s
discussion on the use of natural ventilation:
- Some
criticism has been received that the current level of outside air (7.5
cfm/person) may be contributing to poor air quality, especially in
schools.
- The reason Wisconsin kept the lower amount of
outside air per person was for an energy conservation purpose and it
was established using the minimum square footage per person based on
occupancy.
- It was suggested that currently there are
better energy recovery systems available that were not as readily
available when the 7.5 cfm/person requirement was developed.
-
There was concern raised that a building designed using all natural
ventilation may create other problems, including increased humidity and
extra energy use.
- Some felt that natural ventilation may
work in some small occupied buildings or spaces; however, it may not
work in all buildings and it would be better to mandate only a certain
percentage of natural ventilation in certain buildings.
- It
was noted that if all natural ventilation is provided, it would be
difficult to satisfy the overall needs of the customers, who typically
are looking for a more controlled environment, which would be better
achieved through mechanical ventilation.
- It was noted the
Department needs to justify why a Wisconsin modification is needed that
is different from the IMC. It was explained the HVAC Code
Council will be meeting on Wednesday, February 28th to discuss this
issue as well.
4. Adjournment and update on
future meetings.
It was announced that the CBCC/MDCC meeting
will be meeting on Tuesday, March 27, 2007 to discuss the hearing
comments and agency responses. The meeting, starting at 9:30
am, will be held at the Holiday Inn-Madison East located at 3841 East
Washington Ave., in Madison. Members from this council are
welcome to attend as visitors.
Questions may be
directed to Jim Quast, Program
Manager, 608-266-9292, jquast@commerce.state.wi.us.
Wednesday,
November 16, 2005,
9:30 a.m. to 2 p.m., Department of Safety and Professional Services,
201 W. Washington Ave.,
Room 3C, Madison, Wisconsin
Council member attendance: Jeffrey Boldt P; Dan Dehnert P; Ross DePaola
P; Kevin Lichtfuss P; Dave Osborne P; Gerald Schulz Ex; Harry Sulzer P;
Bob Wiedenhoefer P
Guests: Norman Bair, Wisconsin Department of Administration, Division
of Energy, Don Hynek, Wisconsin Department of Administration, Division
of Energy, Scott Olsen, Madison Gass and Electric
Commerce Staff: Jim Quast, Program Manager; Diane Meredith, Code
Consultant
Welcome and introductions:
Bob Wiedenhoefer opened the meeting with introductions. The
progress report from the previous meeting and the meeting agenda were
accepted as presented.
Division Updates:
Jim Quast explained the Commercial Building Code Council (CBCC) and the
Multifamily Dwelling Code Council (MDCC) will be meeting on December 8
to receive updates from the Energy, HVAC, Alterations and Change of
Occupancy, and Fire Safety and Protection Systems Specialty
Councils. The goal of the Division is to hold public hearings
in
the spring of 2006 on the proposed changes to the Wisconsin Commercial
Building Code (WCBC) for incorporation of the 2006 editions of the ICC
codes. The anticipated effective date of the revised WCBC is
early 2007. Jim noted he hoped that by the end of this Energy
Council meeting that there would be a
recommendation to proceed to public hearings.
Jim noted the following specific updates:
- Erosion control draft is being finalized for public hearings.
- Senate Bill 325 has been introduced that relates to improving indoor
environmental quality in public schools. Under the bill a
special
committee may be formed in the Department to address several aspects of
the bill, including rule development.
- Legislation is being proposed that would require certain installers,
such as elevator and electrical, to be state-licensed. There
is
also some talk of including licensing of building contractors.
- Legislation requiring sprinklering of private university high-rise
housing, sororities and fraternities retroactively passed and will be
phased in over a certain number of years.
- Energy Policy Act has created tax credits for home builders who can
demonstrate their homes are 50 percent better than the International
Energy Conservation Code (IECC).
Review of Final Actions
for changes to the IECC
Jim Quast distributed the challenges to the IECC 2004/2005 change
proposals and a summary of these changes. Of the changes
proposed, the following major changes were noted and the
recommendations made:
- IECC Table 402.1: The thermal envelope insulation value for
“wood frame walls” was revised to R-19 or R-13
(cavity
insulation) + 5 (insulated sheathing) for Zone 6. This change
was
to correct an IECC/IRC inconsistency by using Department of
Energy’s (DOE) original R-values for wood frame walls in the
IECC.
- The members discussed whether the earlier IECC wood frame wall
U-factors of R-21 or R-19 should be maintained and the following motion
was made: Motion was made and seconded to maintain the requirements
under the 2004 Supplement, which included higher U-factors for wood
frame walls as specified under IECC Table 402. The motion
failed
by a vote of 6 to 1.
- Ross DePaloa also noted there was an earlier decision made by the
Council at the May 18 meeting to include a footnote under the
fenestration column that would limit the fenestration to wall ratio to
25 percent, and to include a footnote under the sky-light column to
limit the fenestration to 10 percent of the roof area. Ross
did
not see this change in the proposed draft and it was explained the
inclusion of these modifications are being discussed with Division
management.
- IECC section 803.2.6 and Table 803.2.6 (1): A provision,
which
is consistent with ASHRAE 90.1, was added to address
over-pressurization during economizer operation, and the trigger for
requiring economizers was lowered to less than 54,000 Btu/hr for Zone
6B. The members agreed that Table Comm 63.0803 should be
modified
to require economizers on all simple cooling systems at less than
33,000 Btu/hr and complex cooling systems to less than 54,000 Btu/hr.
- IECC section 803.3.3.4: Revised the language to require
motorized dampers on all outdoor air supply and exhaust ducts that will
automatically shut when the system or a space is not used, and to
permit gravity dampers only under certain conditions. The
members
had a lengthy discussion, which resulted in creating Comm
63.0803(6)(b), to permit gravity dampers only when the outside exhaust
airflows are 300 cfm or less.
- IECC section 805.2.2: The modifications relating to an
occupant
override for lighting controls were clarified, and the lighting power
compliance provisions were simplified to be consistent with ASHRAE
90.1. It was noted that IECC provisions and ASHRAE 90.1
provisions are not exactly the same. The members discussed
whether the lighting controls should be the same for both ASHRAE 90.1
and the IECC and the following motion was made: A motion was
made
and seconded to create a Wisconsin modification that would require
consistent application of the dual lighting controls under IECC section
805.2.2.1 for both ASHRAE 90.1 and the IECC. The motion
carried
by unanimous vote.
- IECC section 805.5.2: The lighting power compliance
provisions
were simplified to be consistent with ASHRAE 90.1. However,
ASHRAE 90.1 section 9.2.2.3 includes additional exceptions, which
should also apply if the IECC is used for compliance. The
members
also discussed that under current Comm 63.1045 3)(a) there are
additional exceptions, such as lighting for amusement and attraction
areas in theme parks, that are not included under the IECC or ASHRAE
90.1 and should they be included as Wisconsin modifications. The
following motion was made: Motion was made and seconded to
create
a Wisconsin modification that would require the exceptions under ASHRAE
90.1 section 9.2.2.3 to apply when the ICC is used. The
motion
passed by unanimous vote.
- Comm 63.0805 (3): The members recommended the lighting
density
as used under the lighting control requirements be changed to 0.8 W/ft2.
Use of the International
Existing Buildings Code (IEBC) and application of energy requirements
Jim Quast updated the members on the proposed adoption of the IEBC,
which includes energy requirements. He distributed excerpts
from
the IEBC relating to energy and explained that alterations and
additions to existing buildings would be required to comply with the
requirements for new construction as specified under the
IECC. It
was noted that these requirements are consistent with ASHRAE 90.1 with
regards to repair and replacement of equipment.
Ventilation Controls
Members discussed whether the code should require ventilation controls
that would operate to reflect the varying occupant load for large
multi-purpose areas such as high school gymnasiums. This
issue
was discussed by the HVAC Specialty Council and was not
accepted. The members discussed that this was an energy conservation
issue but
some indicated the code already provides the flexibility to reduce the
ventilation to areas when the occupant load varies. It was
decided the members were to send Jim information on any proposed
language. Jim noted this recommendation would need to be
reviewed
by management within the Division before any changes are proposed.
Council Recommendation
The members unanimously recommended the adoption of the 2006 IECC with
the proposed Wisconsin modifications and these modifications should be
included in the public hearing rule package for Comm 61 to 66.
Next Meeting:
This Council
will not meet again until after public hearings are held in the spring
of 2006. The CBCC/MDCC meeting will be on Thursday, December
8,
2005 to review all of the proposals from the Division Specialty
Councils. The meeting, starting at 9:30 am, will be held at
the
Holiday Inn-Madison East located at 3841 East Washington Ave., in
Madison. Bob Wiedenhoefer as chairperson is invited to come
to
CBCC/MDCC meeting to represent the Energy Specialty Council, if he so
desires. Other members are welcome to attend as visitors.
Any questions may be directed to Jim Quast, Program Manager,
at
(608) 266-9292, email at jquast@commerce.state.wi.us, or Diane
Meredith, Code Consultant, at (608) 266-8982, or email at
dmeredith@commerce.state.wi.us
Thursday,
September 22,
2005, 9:30 a.m. to 12:30 p.m., Thompson Commerce Building,
201 W. Washington Ave., Room #3B, Madison, Wisconsin
Council Member Attendance: Jeffrey
Boldt – P; Dan Dehnert – P;
Ross DePaola – P; Tim Kritter – Ex; Kevin Lichtfuss
- P; Dave Osborne - P; Gerald
Schulz - P; Harry Sulzer - P;
Bob
Wiedenhoefer – P
Guests: Norman Bair, Wisconsin
Department of Administration,
Division of Energy; Don Hynek, Wisconsin Department of Administration,
Division
of Energy; Scott Olsen, Madison Gas and Electric; Brian Matthys,
Bayfield
Electric Corp.; Jan Stranz, Oconto Electric Corp.; Beata Kalies,
Wisconsin
Federation of Co-ops; Paul Gillis, Dairyland Power Co-op; Tim Semman,
Wisconsin
Builders Association; Joe Nagan, Home Building Technology Services;
Dave
Jenkins, Wisconsin Federation of Co-ops
Commerce staff: Bob DuPont, Program
Development; Greg Jones,
Administrator Safety and Buildings Division; Jim Quast, Program
Manager; Diane
Meredith, Code Consultant; Leroy Stublaski, Integrated Services; Duane
Hubeler,
Integrated Services
Welcome
and introductions
Bob Wiedenhoefer opened the meeting with introductions. Bob DuPont
introduced Greg Jones, who is the
newly appointed Administrator for the Division of Safety and Buildings.
Greg welcomed everyone and
said he was encouraged
to see so many individuals involved with the development of the energy
rules
and looked forward to working with them in the future.
Bob Wiedenhoefer asked for a review
of the agenda and the
progress report from the previous meeting; both were accepted as
written. However,
it was requested that a discussion
on economizers be included on the agenda for the next Council meeting.
Division
Updates
Jim Quast explained the Specialty Councils are meeting to discuss the
ICC
changes that may become part of the 2006 ICC codes and to review
current Wisconsin based
modifications for relevancy. The
Umbrella Councils will be meeting on October 27th and December 8th to
receive
updates on the Specialty Councils recommendations. The goal of the
Division is to hold public
hearings in the spring of 2006 on the proposed changes to the Wisconsin
Commercial Building Code (WCBC) for incorporation of the 2006 editions
of the
ICC codes. date of the revised WCBC is early 2007.
Presentation
from Energy Cooperatives
Bob DuPont and Jim Quast explained the Energy Conservation Code
Council, which
is comprised of energy experts, has been asked to listen to the
concerns the Wisconsin
Electric Cooperatives have with certain Uniform Dwelling Code (UDC)
requirements relating to energy conservation and to provide their
advice.
Dave Jenkins from the Wisconsin
Federation of Cooperatives and Jan Stranz from the Oconto Electrical
Cooperative addressed the Council and indicated they have specific
concerns
with the current requirements for electrically heated homes. They
indicated the purpose
of the
presentation was to ask that the UDC be analyzed to provide fair
treatment of
advanced electric heating options, such as geothermal heat pumps.
The following points and issues were
stated during their
presentation:
- Explained the super-insulation requirement for electrically heated
homes was
based on state laws that were created in 1983. Indicated the UDC
currently requires insulation
requirements of R50 in
the ceiling and R12.5 in the walls of electrically heated homes.
- Identified a concern that the appliance credits available under the
UDC work
with high efficiency gas furnaces but do not work properly when heat
pumps or
radiant heat are used.
- Asked the REScheck and WIScheck software packages be reviewed to
correct the
deficiencies that exist when other heat sources, such as heat pumps,
ground
source heat pumps, or dual fuel systems are used.
- Presented fuel cost comparisons for a sample home using propane gas
and one
using ground source heat pump. The
ground source heat pump system would have fuel costs considerably less
than the
propane gas heat system.
- Indicated that in rural areas of Wisconsin,
natural gas is often unavailable,
leaving only electrical, propane, fuel oil or wood as their choices.
- Suggested that all heating sources used in homes should have the same
insulation levels.
The Council members were generally
not in favor of reducing
the amount of insulation required in homes that use electric resistance
heating
during peak hours. However,
they
indicated that the code should be modified to recognize a home that
uses ground
source electric heat pumps. The
thermal
envelope provisions for this type of heat pump should reflect values
similar to
non-electrically heated homes. It
was
noted that REM/Rate is a software program that recognizes the other
heat
sources; however, most UDC inspectors use REScheck or WIScheck, which
is where
the problem exists. Leroy
Stublaski, UDC
consultant, feels the code under s. Comm 22.21 (3) (d) already
recognizes using
other heat sources but agrees that the programs used to verify
compliance with
the requirements could be improved. It
was suggested that training should be available to the inspectors so
they of
aware of other acceptable software programs and methods besides the
REScheck
and WIScheck software programs.
Use
of the International Residential Code (IRC) for energy
conservation requirements under the UDC
The members discussed using the energy conservation requirements from
the IRC,
which is essentially using the International Energy Conservation
Code(IECC). There
was some concern on the availability of
this code to the general users of the code, and that the IRC/IECC does
not address
an overall U-value for a dwelling. They
also wanted to know how the code would apply to the concerns discussed
earlier relating
to the use of other heating sources, and how REScheck would work with
the IECC.
Bob DuPont asked which members of
this Council would be interested
to study energy issues under the UDC. The
following people offered to be part of the work group to study the UDC
issues: Ross
DePaola, Dave Osborne, Harry Sulzer, Bob Wiedenhoefer
Homework
assignments: Ross DePaola will check on the REScheck
program and its use in the IRC.
Next
meeting: The next meeting of the Energy Conservation
Code Council is scheduled for Tuesday, November 16th to discuss
potential changes
to the WCBC for incorporation of the 2006 IECC.
Any questions may be directed to Jim
Quast, Program Manager,
at (608) 266-9292, jquast@commerce.state.wi.us,
or Diane Meredith,
Code Consultant, at (608) 266-8982, dmeredith@commerce.state.wi.us
Wednesday,
May 18, 2005, 9:30
a.m. to 2:10 p.m., Department of Safety and Professional Services, 201
W. Washington Ave., Room
3B, Madison, Wisconsin
Council Member Attendance: Jeffrey Boldt P; Dan Dehnert P;
Ross DePaola P; Tim Kritter Ex; Kevin Lichtfuss A; Dave Osborne P;
Gerald Schulz Ex; Harry Sulzer P; Bob Wiedenhoefer P
Guests:Jim Boullion, AGC of Wisconsin; Scott Olsen, MGE
Commerce Staff: Jim Quast, Program Manager; Diane Meredith,
Code Consultant; John Spalding, Integrated Services
Welcome and
introductions: Bob Wiedenhoefer opened the meeting with
a review of the agenda and the progress report from the previous
meeting, both were accepted as written.
Division
Updates
Jim Quast reported Kimberly Walker, Division
administrator, is leaving Safety and Buildings to take the position of
Division Administrator for the Division of Energy in the Department of
Administration. Kimberly’s last day with the Division is May
27th.
Jim noted that the HVAC Advisory Code Council would be meeting
on June 14th to discuss ventilation issues. Jim explained the one-and
two-family dwelling code inspection program of contracting with outside
providers and this model might be reviewed for use with commercial
buildings in the future. Members expressed concern that there must be a
monitoring system in place so consistency in application and
enforcement can be achieved when outside providers are used. Jim noted
that consistency is a problem with the current enforcement process, and
that monitoring is necessary with any enforcement system.
John Spalding reported the plan reviews are keeping within the
target timeframes. He also indicated the Web scheduling system will
start in early July and after the system is stabilized, the fax
scheduling would be eliminated.
Discussion of Current Wisconsin Modifications
under Comm 63 subchapter III
Jim Quast explained that after today’s
meeting, staff members would start work on a proposed hearing draft
with the modifications proposed to the IECC that would be available in
late summer. The group would still need to review the IECC 2004/2005
proposed changes and the final ICC determinations would be decided at
their meetings in fall.
The following code sections were discussed and the Council
recommendations are noted:
1. Comm 63.0001 to 63.0004
Purpose, scope and application
The administration and enforcement requirements under IECC chapter 1
will be reviewed by staff for potential placement under chapter Comm
61, which is the general chapter on administration and enforcement for
the entire Wisconsin Commercial Building Code (WCBC). Jim noted the
IECC is organized and formatted such that the general application
section contains some specific technical requirements that should
probably be maintained under chapter Comm 63.
2. Comm 63.1050 Lighting Controls
The members discussed the
lighting comparison tables prepared by Jim Quast, which included a
comparison of the current Comm 63 requirements to the California 2005
code, the IECC and the ASHRAE 90.1 standard. Ross DePaola explained the
purpose behind the current lighting control requirements under Comm 63
is to provide designers with flexibility in lighting design by allowing
trade-off for lighting levels. The IECC and ASHRAE 90.1 standard have
decreased the lighting levels to save energy and some members felt the
current control requirements would provide the flexibility for
designers to allow increased lighting in some areas when lighting
controls are provided. Some members also expressed the desire for the
code providing some type of daylighting incentives.
The members proposed the following requirements for lighting:
Use the IECC or ASHRAE 90.1 standard for lighting requirements
with the following modifications required if either model is used:
- Maintain the lighting control requirements for dual
switching specified under Comm 63.1050 (2) (a)
- Maintain the daylighting requirements specified under Comm 63.1050 (3)
(Staff to research whether the “daylighting area”
definition parameters in conjunction with Comm 63.1050 (3) create
“barriers” for deep-daylit spaces.)
- Limit one parameter for retail lighting for displays to 50 percent of
the floor area. (Note: Monitor IECC proposed revisions #99-04/05 and
#101-04/05.)
3. IECC section 803 relating to minimum equipment efficiencies
It was reported that the Department of Energy (DOE)
regulations relating to minimum efficiency requirements for the
manufacture of mechanical equipment are to take effect January 23,
2006. Staff members will monitor the IECC changes to see that the new
ratings are consistent with these DOE regulations.
4. Table 63.0803 Economizer Requirements
It was discussed that economizers should be required on all
rooftop units that have a capacity greater than 3-ton capacity. The
energy savings by providing economizers, especially on all rooftop
units, would offset the cost to provide the economizers. It was
proposed to change the Table 63.0803, 2nd line/2nd column to read:
“Economizers on all cooling systems 33,000
Btu/hr.”
5. IECC Table 402.1 relating to fenestration
A concern was raised relating to the amount of fenestration
permitted under IECC Table 402.1. It was discussed the amount of
fenestration is not limited under the IECC and to maintain energy
conservation savings the following motion was made:
A motion was made and seconded to:
- create footnote h under IECC Table 402.1, column
“fenestration U-factor” that reads:
h. The fenestration shall not exceed 25% of window to wall ratio
- create footnote i. under “Skylight
U-factor” that reads:
i. The fenestration shall not exceed 10% of the roof area.
The motion passed by unanimous vote.
Homework
assignments The following assignment was given
for completion by the next meeting:
All members are to review the
IECC 2004/2005 proposed changes. The IECC Committee decisions to the
20004/2005 changes were distributed to the members earlier. Staff will
prepare a proposed draft of modifications that will be included when
the 2006 IECC is adopted.
Next meeting The next meeting will be
scheduled
sometime in late summer or early fall. The proposed draft of changes to
the IECC will be mailed to the members for their consideration prior to
the next meeting.
Tuesday,
April
12, 2005, 9:30 a.m. to 2 p.m., Department of Safety and
Professional Services,
201 W. Washington Ave., Room 3B, Madison, Wisconsin
Council member attendance: Jeffrey Boldt P; Dan Dehnert P;
Ross
DePaola P; Tim Kritter Ex; Kevin Lichtfuss A; Dave Osborne P; Gerald
Schulz P; Harry Sulzer P; Bob Wiedenhoefer Pu
Guests: Don Hynek, Wisconsin DOA-Division of Energy; Scott
Olsen,
Madison Gas and Electric
Commerce staff: Jim Quast, Program Manager; Diane Meredith,
Code
Consultant; John Spalding, Section Chief
Welcome and
introductions
Jim Quast opened the meeting with a review of the agenda and the
progress report from the previous meeting, both were accepted as
written.
Division
Updates
Jim Quast noted there were no updates to report and
indicated
that plan review processes were within the targeted timeframes.
Discussion of Current Wisconsin
Modifications
under Comm 63
subchapter III
Jim explained that under the IECC designers are given a
choice
model for commercial buildings to use either IECC chapter 8 or the
referenced ASHRAE 90.1 standard. The requirements under Comm 63,
Subchapter III replaced the referenced 1989 edition of the AHSRAE 990.1
standard. The current requirements of Comm 63, Subchapter III were
based upon developing work for the 1999 ASHRAE 90.1 standard. The IECC
2006 edition will reference the 2004 edition of the ASHRAE 90.1
standard. Jim explained that it is the Division’s premise
that
the separate Comm 63, Subchapter III is no longer necessary and that
any necessary Wisconsin requirement from the subchapter can be retained
and relocated as a modification to the IECC.
The following code sections were discussed and the Council
recommendations are noted:
- Comm 63.1027 Zone Controls and 63.1028 Humidity
Controls
Delete these requirements under this chapter and defer them to the HVAC
Council.
- Comm 63.1029 Insulation, materials and construction
Delete these requirements since they are covered under
ASHRAE 90.1
standard.
- Comm 63.1030 Hydronic System Controls
Delete this requirement since it just cross-references the IECC
requirement.
- Comm 63.1032 Motor Efficiencies
The members discussed whether all motor efficiencies are already
required to comply with the Energy Policy Act (EPAct) of 1992, which
would not be different from the ASHRAE 90.1 Table. Don Hynek from DOA
offered to provide staff with the EPAct information on the motor
efficiencies. If motor efficiency is a minimum federal requirement, it
was suggested to put an informational note in Comm 63 and include the
EPAct Table in the Appendix.
- Comm 63.1060 Nondepletable Energy Source and
63.1070 System
Analysis Design
Delete these requirements since they are covered in the ASHRAE 90.1
standard.
- Comm 63.1040 to
63.1050 Lighting
Requirements
Ross DePaola distributed information from a study group on the lighting
requirements and indicated there are inconsistencies between the IECC
and the ASHRAE 90.1 standard and recommended that the lighting
requirements remain as Wisconsin modifications and suggested reprinting
tables in the IECC and ASHRAE 90.1 standard. The recommendations
included:
- Maintain the current Comm 63
requirements
relating to lighting controls, lighting adjustment factors, which were
based upon California’s energy code
- Retain and modify the current Comm 63 Table with lighting control
credits
- Revise the current interior lighting power budget requirements
- Modify the daylighting controls
- Eliminate the current Complete Building Method relating to lighting
power allowance
- Eliminate the Area Factor Tables under Comm 63.1049 and adopt the
IECC Tables for building area method
- Adopt ASHRAE 90.1 requirements for exterior lighting power and
consider adopting requirements mandating Pulse-Start ballasts for HID
fixtures.
- Reduce exit light watts to match IECC and ASHRAE 90.1
Jim Quast explained again that the IECC will be adopted by
reference
as the base standards and the need to reprint Tables or requirements
from the IECC or ASHRAE 90.1 is not necessary. Even though some members
felt that it would be easier to have all of the lighting requirements
in one area, others felt that the number of Wisconsin modifications
should be kept to a minimum when using IECC or ASHRAE 90.1. It was also
noted that the IECC together with the ASHRAE 90.1 standard provides
flexibility in design without minimizing the energy conservation of a
building. Also noted was that IECC/ASHRAE cover the same matters as the
current Wisconsin lighting requirements other than the lighting power
adjustment alternatives and that the 2006 IEEC/ASHRAE power densities
reflect greater energy savings.
It was decided that staff
members would
do a comparison of the lighting controls that are under Comm
63-Subchapter III, IECC and ASHRAE 90.1 and have it available for the
next meeting. The members did agree that the IECC should be used
without reprinting all of the lighting requirements but identified the
following issues to be discussed at the next meeting:
- Comm 63.1045 relating to the calculation of interior lighting power
- Comm 63.1045 (2), Table 1045 and Comm 63.1051
- Comm 63.1050 should be reviewed to identify any specific requirements
for retention
Review of 2004 ICC Changes
The
members reviewed
the changes contained under the 2004 IECC Supplement and identified the
following:
- Delete IECC section 401.3
relating to
certificate requirements to be included at the electrical panels for
low-rise residential buildings. It was felt that in most cases the
certificate requirement would not benefit the tenants in residential
buildings.
- Ross was concerned that residential buildings could use an all glass
wall under IECC section 402.3 because there is no overall U-value.
However, the members recommended maintaining the IECC section 402.3
relating to fenestration.
- As determined earlier, IECC section 402.5 relating to moisture
control will be modified.
- Noted that any changes made to lighting controls will also require
changes under IECC section 802.1 relating to general building envelope
requirements.
- IECC section 803.2.5.1 relating to energy recovery ventilation
systems will be reviewed to see whether the requirements overlap with
the economizer requirements.
Homework assignments
The following assignments were given for completion by
the
next meeting:
- Staff members will contact Don Hynek from DOA for information on the
EPAct requirements.
- Staff members will prepare a comparison on lighting issues.
- All members are to review the IECC 2004/2005 proposed changes. The
IECC decisions on the proposals were distributed.
Next meeting
The next meeting has been scheduled for Wednesday, May
18,
2005 in conference room #3B in the Thompson Commerce Center, 201 W.
Washington Ave., in Madison.
Tuesday,
March
15, 2005,
9:30 a.m. - 2 p.m., Thompson Commerce Center, Room 3B, 201 W.
Washington Ave., Madison, Wisconsin
Council Memeber Attednace: Jeffrey Boldt Ex; Dan Dehnert Ex;
Ross
DePaola P; Tim Kritter A; Kevin Lichtfuss P; Dave Osborne P; Gerald
Shulz Ex; Harry Sulzer P; Bob Wiedenhoefer P
Guests: Don Hynek, Wisconsin DOA-Division of Energy; Scott
Olsen, MGE
Department of Safety and Professional
Services
Staff: Jim Quast,
Diane Meredith, John Spalding,
Welcome and
introductions: Bob
Wiedenhoefer opened the meeting with a round of introductions. The
progress report from the previous meeting and the meeting agenda were
accepted as presented. (Please note that Dan Dehnert should be been
marked excused rather than absent from the 2/08/05 meeting.)
Division
Updates
Jim Quast noted the ICC
organization has
included the Wisconsin Enrolled Commercial Building Code (WECBC) on
their Web site for reviewing. This ICC decision to provide this on
their Web site may have resulted from a federal Court decision in Texas
that ruled once a state or municipality adopts a model code, the
copyright restrictions do not apply. It was noted that this federal
Court decision would only apply to the federal Court district where the
decision was made.
Jim explained the Division of Safety and Buildings’
was asked
to develop a plan for how it would reduce its budget by 10-percent
spending authority and 10-percent staffing positions, if required to do
so. The staffing positions in the Division of Safety and Buildings
would need to be reduced by approximately 21 people. Most of these cuts
would be in vacant positions. John Spalding indicated that currently
the Division has 14 inspectors who perform commercial inspections.
Jim indicated that in accordance with s. 101.651, Stats., the
Uniform Dwelling Code, as of January 1, 2005, is being enforced in
every community. The law required that where communities do not have
enforcement or inspection authority for one-and two-family dwellings,
the state must provide the inspection services. The Department has
contracted with 24 inspector groups to perform these inspection
requests. Jim also noted that the UDC inspection process is not the
same for commercial buildings, which does not mandate an inspection
before an occupancy permit is issued.
Discussion of Current Wisconsin Modifications
under Comm 63
subchapter III
Jim Quast explained to the members that it is the Division’s
recommendation to eliminate all of the requirements under Comm 63,
Subchapter III since these requirements were only included because the
ASHRAE 90.1 standard-1989 version was referenced under the 2000 edition
of the IECC. The requirements in Comm 63, Subchapter III were
considered improvements over the 1989 edition of AHSRAE 90.1 standard;
however, since a newer version of ASHRAE 90.1 standard, most likely the
2004 edition, will be referenced under the 2006 IECC, the current
requirements could be eliminated.
The following code sections were discussed and the Council
recommendations are noted:
1. Comm 63.1001 Application
Hold the final decision on the requirements under Comm 63.1001 for
discussion with the general application and enforcement requirements.
2. Comm 63.1005 Definitions
Delete the definition section
and include
any unique definitions under IECC section 200.
3. Comm 63.1010 Exempt
Buildings
The requirements under Comm
63.1010 will be
discussed with the general application and enforcement requirements.
4. Comm 63.1011 Air Leakage
Delete the requirements
relating to air
leakage since they are covered under IECC sections 802.
5. Comm 63.1012 Daylight
Credits for
Skylights
Delete the requirements
relating to
daylight credits for skylights since the current requirements are not
substantive for application.
6. Comm 63.1014 Building
Envelope
Thermal Performance
Delete the requirements
relating to
building envelopes since these requirements are covered under IECC
section 806.
7. Comm 63.1015 Component
Standards
Option
Delete this section relating
to component
standards for building-envelope thermal performance since these
requirements are covered under IECC section 806.
8. Comm 63.1016 System
Standards Option
Delete
this section
relating to system standards for building-envelope thermal performance
since these requirements are covered under IECC section 806.
9. Comm 63.1017 Design Criteria
Delete this section relating
to system
standards for thermal performance values for the exterior envelope for
certain buildings since these requirements are covered under IECC
section 802.
10. Comm 63.1018 Material
Properties
Maintain the requirements
under this
section relating to test methods for determining thermal properties of
materials.
11. Comm 63.1019 Required
Calculation
Procedures
Delete these prescriptive
requirements
relating to calculation procedures for thermal performance since the
requirements under IECC section 801.2 are adequate.
12. Comm 63.1020 Minimum
Equipment
Efficiencies
Hold off on the final decision
until more
information is received relating to a federal law that requires a
higher SEER efficiency rating than specified under the IECC. Don Hynek
from DOA offered to provide a copy of the federal law to staff members.
13. Comm 63.1021
Field-Assembled
Equipment and Components
Delete the requirement
relating to
component efficiencies since a similar requirement is covered under
IECC section 102.
14. Comm 63.1022 Heat Pump
Equipment
Controls
Delete the requirements
relating to heat
pumps that are equipped with supplementary heaters since these
requirements are already covered under IECC section 803.
15. Comm 63.1023 Load
Calculations for
Sizing and Comm 63.1024 System and Equipment Sizing
Hold the final decision on
these
requirements relating to sizing of systems and equipment since the
requirements appear to overlap with requirements in Comm 64 relating to
HVAC. The members are to review the requirements under IECC 803.2 and
803.3 for consistency with these rules.
16. Comm 63.1026
Temperature Controls
and Comm 63.1027 Zone Controls
Delete
these
requirements relating to HVAC systems and control devices for
temperatures and zone controls since these requirements are covered
under IECC section 803.
Homework
assignments The following assignments were
given for
completion by the next meeting:
- Staff members will contact
Don Hynek from
DOA for information on a federal law requiring a higher SEER efficiency
rating.
- All members will identify any requirements besides the lighting
requirements that may need to be retained from Comm 63.1028 to 63.1032,
and Comm 63.1060 and 63.1070.
- Ross DePaola will share material on the lighting systems.
- All members are to review the IECC 2004 for any other issues that may
need to be discussed.
Next meeting: The next
meeting has been
scheduled for Tuesday, April 12, 2005 in conference room #3B in the
Thompson Commerce Center, 201 W. Washington Ave., in Madison.
Tuesday, February 8, 2005,
9:30
a.m. to 2 p.m.,
Thompson Commerce Center, Room #3B, 201 W. Washington Ave., Madison.
Council Member Attendance: Jeffrey Boldt P; Dan Dehnert Ex;
Ross
DePaola P; Tim Kritter A; Kevin Lichtfuss (Alt. Gerry Schnelle) P; Dave
Osborne P; Gerald Shulz A; Harry Sulzer (Alt. Jim Wolf) P; Bob
Wiedenhoefer P
Guests: Don Hynek, Wisconsin DOA-Division of Energy; Scott
Olsen, MGE
Depatment of Commerce staff: Jim Quast, Diane Meredith, John
Spalding
Welcome and introductions
Bob Wiedenhoefer opened the meeting with a round of introductions. The
meeting summary from the previous meeting and the meeting agenda were
accepted as presented.
Division Updates
Copies of the revised chapters Comm 61 to 65, Wisconsin Commercial
Building Code, and the adopted copy of the rule changes, which contains
the analysis of the rule changes, were distributed to the members. Jim
Quast explained that insert pages containing the codes that have been
modified are available on the Web site for use with the Wisconsin
Enrolled Code. Jim also noted that the Wisconsin Enrolled Code is
available for viewing at the International Code Council’s Web
site: www.iccsafe.org.
Jim indicated that several of the specialty councils reviewing
updates for the future adoption of the 2006 ICC codes are continuing
their work. He noted that the HVAC Code Council would discuss
ventilation issues, such as dampering and natural ventilation, at an
upcoming meeting.
Jim reported that the WE Energies Building Code Collaborative
has
discussed daylighting issues and it is their belief that provisions
necessitating daylighting, if any, would be better placed in the
Building Code rather than the Energy Code. Some Council members felt
the Building Code is to be a minimum code for energy conservation and
should not become a design tool that restricts designers to only a few
design options.
Presentation from Scott Olsen
Scot Olsen, who is an efficiency engineer from Madison Gas and Electric
(MGE) identified the following energy issues for consideration by this
Council.
1. Focus on outdoor air ventilation rate for large occupancy
spaces
where the occupant load changes.
2. Suggests adopting the IECC lighting power densities and maintain the
separate controls for non-daylighting areas in a building. He also
suggests maintaining occupancy sensors for daylighting spaces.
3. Provided a comparison chart supporting the savings that would be
obtained for rooftop air conditioning and condensing units using the
IECC-2003 code or the ASHRAE 90.1-2001 standard over the current energy
code.
4. Suggests that natural ventilation not be restricted but allow it
only with careful consideration. Some members felt that energy recovery
is the only answer for use of natural ventilation.
5. Recommends that the Energy code ensures that modulation of air
changes per hour of supply air be allowed.
Discussion of Current Wisconsin Modifications
The following code sections were discussed and the Council
recommendations are noted:
Comm 63.0802 (2) Moisture Control
The members discussed whether foam insulation with a perm rating one 1
would also require a vapor retarder. It was noted that providing this
type of insulation would not require the vapor retarder and that the
code is written such that it would be acceptable without making a
specific modification. It was suggested that the same modification be
made to IECC 802.1.2 for commercial buildings as made under IECC 402.5
for residential buildings, which is to eliminate the words
“not
ventilated to allow moisture to escape.”
Comm 63.0802 (3) [IECC 802.2.4] Roof Assembly
Delete the modification since the members feel that the Wisconsin
requirement is too vague and does not provide any improvements to the
IECC requirements.
Comm 63.0802 (4) [IECC 802.3.2] Sealing of the Building
Envelope
Delete the modification since recessed luminaries are specifically
addressed under IEEC section 802.3.7.
Comm 63.0803 (1) [IECC 803.1] Electrical motors
It was suggested to contact people who would use these requirements to
see whether the electric motor efficiencies are still needed. Jeff
Boldt indicated that ASHRAE 90.1 standard may cover electric motor
efficiencies. This item will be put on hold until the next meeting.
Comm 63.0803 (2) (a) [IECC 803.2.1.1] Simple HVAC Systems and
Equipment
Keep the same Wisconsin modification, which permits the heating and
cooling equipment to be oversized to the calculated load.
Comm 63.0803 (2) (b) [IECC 803.2.3.1] Temperature Controls
Retain the Wisconsin modification and the IECC exceptions. It was
suggested to rewrite the entire requirement including the exceptions so
the entire requirement text is in one place.
Comm 63.0803 (2) (c) [IECC 803.2.3.2] Humidity Controls
Delete the modification but request that this topic be discussed with
the HVAC Council.
Comm 63.0803 (2) (d) [IECC 803.2.6] Cooling with outdoor air
Revise the current modification requiring economizer controls retaining
basically the current triggers, but modifying IECC Table 803.2.6 (1) by
adding zones 6A and 7. It was suggested to reprint the entire Table so
all of the text is in one place.
Comm 63.0803 (2) (e) [IECC 803.2.7] Shutoff dampers
Maintain the modification that requires that automatic or gravity
dampers be provided on all outdoor air intakes.
Comm 63.0803 (2) (f) [IECC 803.2.8] Duct and plenum insulation
Maintain current modification relating to the insulation of all supply
ducts and return air ducts and plenums but change the R-7.5 insulation
rating to R-8.
Comm 63.0803 (3) (a) [IECC 803.3.1.1] Equipment and system
sizing
Maintain the Wisconsin modification, which permits the heating and
cooling equipment to be oversized to the calculated load.
Comm 63.0803 (3) (b) [IECC 803.3.3.4] Shutoff damper controls
Maintain the modification but eliminate the word
“gravity”
since it is redundant with automatic dampers.
Comm 63.0803 (3) (c) [IECC 803.3.3.5] Economizers
Maintain the modification relating to economizers on fan systems and
make it the same as proposed under IECC 803.2.6.
Comm 63.0803 (3) (d) [IECC 803.3.7] Piping Insulation
Delete Table 63.1029 relating to pipe insulation and cross-reference
the requirements in the ASHRAE 90.1 standard, which contains all of the
requirements currently contained under Table 63.1029.
Comm 63.0803 (3) (e) [IECC 803.3.8, 803.3.8.1 to 803.3.8.3]
HVAC
System Completion
Delete the current modification relating to balancing and documentation
of HVAC systems and replace it with a requirement that states the IEEC
requirement does not apply. This requirement is covered under the IMC.
Comm 63.0804 (1) [IECC 804.3] Temperature Controls
Maintain the current modification, which states that the IECC
requirement relating to temperature controls is not included in
Wisconsin.
Comm 63.0804 (2) [IECC 804.4] Heat Traps
Delete the current modification and change it to state that the IECC
requirement relating to heat traps does not apply in Wisconsin. The
members felt this requirement if used should go under the Plumbing Code.
Comm 63.0804 (3) [IECC 804.5] Plumbing Piping Insulation
Delete Table 63.1029 relating to pipe insulation and cross-reference
the requirements in the ASHRAE 90.1 standard, which contains all of the
requirements currently contained under Table 63.1029.
Comm 63.0805 [IECC 805] Lighting Systems
It was suggested that a subgroup be formed to study the lighting
requirements. Ross DeDePaloa will take the lead on gathering
information for consideration by this council.
Comm 63, Subchapter III [Comm 63.1001 to 63.1070] Building
Design
for Commercial Buildings
The council members by consensus feel that Comm 63, subchapter III,
could be eliminated except for certain requirements relating to
lighting. Members are to review the requirements in this subchapter and
identify any other requirements besides lighting that may need to be
retained.
Homework assignments
The following assignments were given for completion by the next meeting:
- Jeff Boldt will share a copy information from the ASHRAE 90.1
standard relating to plumbing and piping insulation, and also
information on electric motors.
- Ross DePaola will share material on the lighting systems.
A- ll members will identify any requirements besides the lighting
requirements under Comm 63, subchapter III that may need to be retained.
- All members are to review the IECC 2004 for any other issues that may
need to be discussed.
Next meeting: The next meeting
has been scheduled
for Tuesday, March 15, 2005 in conference room 3B in the Thompson
Commerce Center, 201 W. Washington Ave., in Madison.
Tuesday, December 7, 2004,
9:30
a.m. - 2:15 p.m.,
Thompson Commerce Center Conference Room #3B, 201 W. Washington Ave.
Madison, WI 53703
Council Member Attendance:Jeffrey Boldt P; Dan Dehnert P; Ross
DePaola P; Tim Kritter Ex; Kevin Lichtfuss P; Dave Osborne P; Gerald
Shulz P; Harry Sulzer P;
Bob Wiedenhoefer P
Guests: Don Hynek, Wisconsin DOA-Division of Energy; Todd
Stuart,
Senator Robert Cowles Office; Jim Boullion, AGC of Wisconsin;
Abbey Vogen, Energy Center of Wisconsin
Commerce Staff: Jim Quast,
Diane
Meredith, John Spalding
Welcome and
introductions
Jim Quast opened the meeting with a round of introductions. Jim noted
there would be a change in the agenda because Scott Olsen was unable to
address the council and he would be invited to the next meeting,
otherwise the agenda was approved as proposed. The progress report from
the previous meeting was also approved as presented.
Election of Chairperson
Bob Wiedenhoeffer was elected chairperson for the council.
Division Updates
Jim reported that the miscellaneous update package to chapters Comm 61
to 65 would have an effective date of January 1, 2005. The council was
provided excerpts from this rule package that related to chapter Comm
63. It was noted that chapter Comm 70, Historic Building Code, would
also become effective on January 1, 2005.
Jim indicated that several of the specialty councils reviewing
updates for the future adoption of the 2006 ICC codes have started
their work. A new code council is in the process of being formed to
review code material related to alteration or change of use to existing
buildings. That council hopes to meet early next year.
Presentation from Todd Stuart
Todd Stuart, Policy Advisor to Senator Robert Cowles, along with Abby
Vogen from the Wisconsin Energy Center presented material on energy
issues the Senator’s office would like to see this council
address. Todd explained Senator Cowles is the head of the legislative
Energy Committee and he would like to see the Department’s
Energy
Council members discuss and consider including requirements for
daylighting and solar water heating rather than creating legislation.
The legislative Energy Committee is concerned with the increase in the
cost of energy to the all citizens and would like to see Wisconsin keep
up with current energy practices.
Todd noted that daylighting, which is a method to light
buildings
using natural light, is not a new method and many state buildings are
already using cool daylighting. Abbey distributed a study concerning
the potential energy savings using daylighting, and Todd also explained
there are Wisconsin solar companies that provide customers with hot
water at energy cost savings. While there may be other new technologies
for consideration, the Senator’s office is only requesting
that
the daylighting and solar water heating concepts be explored for
possible inclusion in chapter Comm 63.
Discussion of Current Wisconsin Modifications
The following code sections were discussed and the Council
recommendations are noted:
Comm 63.0101 through 63.0107 Purpose, Scope, Application and
Compliance
It was suggested that staff review the need for keeping the
administration and enforcement requirements under chapter Comm 63 or
whether there would be a benefit to move them to the chapter Comm 61,
which contains all of the administration and enforcement requirements
for the Wisconsin Commercial Building Code. Eliminate the terminology
of “residential building, Type A-1” as used under
Comm
63.004 (2) (b).
Comm 63.0202 Definition
Delete the definitions of “circulating system”
since this
term is no longer used in the IECC.
Staff members are to review the definition of “code
official” to determine whether a global replacement of the
term
would be appropriate in chapter Comm 63 and the IECC.
Comm 63.0302 Weather Adjustments
Replace the term “code official” with
“department” for who should determine the annual
energy-usage calculation-tool.
Comm 63.0502 (1) [IECC 402.5] Moisture Control
Delete the current modification. Use the new IECC 402.5 requirement but
eliminate the following wording in the 2nd sentence: “not
ventilated to allow moisture to escape,” thereby requiring a
vapor retarder in all situations.
Comm 63.0502 (2) Floors Over Unheated Spaces and Comm 63.0502
(3)
Floors
Delete both of these modifications since the wording under the new IECC
402.5 is acceptable.
Comm 63.0503 (1) [IECC 403.6] Equipment Sizing
It was suggested that staff members research the ACCA manual that is
ultimately referenced. This item will be held for further discussion.
Comm 63.0503 (2) (a) [IECC 403.3 and 403.4] Piping Insulation
The new IECC requirements appear to simplify the minimum insulation
requirements; however, there is concern that using these new
requirements may not achieve the current levels of energy savings. This
item will be held for further discussion as there are proposed IECC
revisions concerning this issue.
Comm 63.0503 (2) (b) [IECC 403.2] Duct Insulation
Delete the current modification. Hold off on proposing any modification
to IECC 403.2 until the commercial requirements are discussed.
Comm 63.0503 (2) (c) and (d) [IECC 403.2.2] Sealing
Delete the current modifications since the new IECC 403.2.2 is
acceptable.
Comm 63.0503 (2) (e) [IECC 403.5] Mechanical Ventilation
Maintain current modification relating to automatic dampers on outdoor
air intakes.
Comm 63.0503 (2) (f) Balancing
Delete the current modification since it is covered under the
International Mechanical Code (IMC)
Comm 63.0504 (1) Combination Service Water-heating and
Space-heating
Boilers
Delete the current modification since the subject is not addressed
under the latest IECC edition.
Comm 63.0504 (2) [IECC 403.4] Pipe Insulation
This item will be held for further discussion.
Comm 63.0504 (3) Swimming Pools
Delete the current modification since they are no longer included under
chapter 4 of the IECC.
Comm 63.0505 Lighting Power Budget
This item will be held for further discussion with all of the lighting
issues.
Comm 63.0602 (1) [IECC 402.1 and Table 402.1] Floors over
Outside Air
Delete the current modification since it is covered under the new IECC
requirements.
Comm 63.0602 (2) Caulking, Sealants and Gasketing
Delete the current requirement since IECC chapter 4 contains no
specific requirements for lighting.
Comm 63.0701 Use of ASHRAE 90.1
Delete the current requirement since the reference to use the ASHRAE
90.1 standard is referenced under IECC chapter 8.
Comm 63.0802 (1) Greenhouses
The modification will be retained since there is no similar requirement
under IECC 801.2
Homework assignment
As homework, members are to
continue to
review and evaluate the current Wisconsin Energy Code modifications to
see whether they could be eliminated or need to be revised in light of
the 2003 and 2004 IECC changes.
Next meeting
The next meeting has been
scheduled for
Tuesday, February 8, 2005 in conference room #3B in the Thompson
Commerce Center, 201 W. Washington Ave., in Madison.
Thursday,
October 7, 2004,
9:30 a.m. to 1:30 p.m., Thompson Commerce Center, Room 3B, 201 W.
Washington Ave., Madison, Wisconsin
Council Member Attendance:Jeffrey Boldt, Present; Dan Dehnert,
Present; Ross DePaola, Present; Tim Kritter, Present; Kevin Lichtfuss,
Present; Dave Osborne, Present; Gerald Shulz, Excused; Harry Sulzer,
Present; Bob Wiedenhoefer, Excused;
Guests: Don Hynek, Wisconsin DOA-Energy; Pradip Tolat,
Wisconsin
DOA-DSF; Lisa Roys, Ruder Ware; Bill Babcock, AIA Wisconsin; Scott
Olsen, MGE
Safety and Buildings Division Staff: Jim Quast, Diane
Meredith, John
Spalding, Randy Dahmen
Welcome and introductions
Jim Quast opened the meeting by welcoming the members and thanking them
for volunteering their time and expertise to participate on the
division’s Energy Conservation Code Council. He noted that
the
last time this group met the task was to review the energy requirements
under the 2000 edition of the International Energy Conservation Code
(IECC) for adoption in Wisconsin. That endeavor was much more
encompassing at that time since using a model building code was a new
concept. Now the goal of this group is to review the changes made in
the 2003 IECC as well as the 2004 Supplement in anticipation of
adopting the 2006 edition of the IECC, and to also review the existing
Wisconsin-based requirements for need. The projected effective date of
the WCBC, which would adopt the 2006 IECC would be July 2007.
The Division’s Advisory Council Manual was
distributed and
explained to the members. It was also noted that the final work of this
Council would be forwarded to the umbrella councils for their review.
The umbrella council review of this group’s initial
recommendations will begin early next year.
Discussion of Projected Work and Summary Sheets
Jim Quast explained the energy handout material and pointed out that
the summaries are staff’s analysis of the changes and
encouraged
the members to review the actual code language. The major change to the
energy rules under the 2004 ICC Supplement was the elimination of IECC
chapters 5 and 6 relating to residential buildings and the
consolidation and simplification of the energy requirements for
low-rise residential buildings. It was Jim’s understanding
that
the residential changes under the 2003 IECC or the 2004 ICC Supplement
would not be considered major or significant from the current energy
requirements.
Jim explained that the most significant impact in light of the
IECC
changes may be to subchapter III of Comm 63. This subchapter provided
alternate energy standards for commercial buildings based upon the 1999
edition of ASHRAE 90.1 standard. The 2003 IECC now references and
reflects the 2001 edition of the ASHRAE standard. It is also
Jim’s understanding that the 2004 ASHRAE standard will be
proposed to be incorporated into the 2006 IECC. Therefore, one matter
for the council to consider would be the possible elimination of Comm
63 subchapter III. The ASHRAE standards will not be provided for each
member; however, if the members feel there certain sections within the
ASHRAE standards that need to be reviewed or discussed, staff will make
copies of these sections for their review.
Jim also indicated there a few other groups working on energy
issues
and the work of these committees might affect the work of this Council.
The We Energies Code Collaborative and the Governor’s Energy
Conservation Task Force are recommending modifications relating to
lighting and building envelope requirements. The members discussed
whether a separate subcommittee or task group could be formed with
experts to research and propose requirements for lighting, and Jim
expressed that it could be a possibility.
Identification of future discussion items
The following issues for further discussion were identified at the
meeting:
Lighting controls
Building envelope requirements
Insulation, vapor barriers and condensation occurring at below-grade
walls
Coordination of energy rules with other model codes, such as the
National Electrical Code for lighting levels
Exterior lighting levels
Ensuring that any modifications or additions to the IECC are enforceable
Daylighting concepts
Jim Quast encouraged the members to review the 2003 and 2004
IECC
changes with their organization so any issues or concerns raised by
their members could also be discussed at the next meeting.
Chairperson
The selection of the chairperson was postponed until the next meeting.
Members expressed a preference of having Bob Wiedenhoefer serve as the
chair.
Homework assignment:
As homework, members are to review and evaluate the current Wisconsin
Energy Code modifications to see whether they could be eliminated or
need to be revised in light of the 2003 and 2004 IECC changes.
Next meeting
The next meeting has been scheduled for Tuesday, December 7, 2004 in
conference room #3B in the Thompson Commerce Center, 201 W. Washington
Ave., Madison.
Questions concerning the meeting may be directed to Diane
Meredith,
Safety and Buildings Division, Department of Safety and Professional
Services, 608-266-8982, or
TDD Relay dial 711 in Wisconsin or 800-947-3529, dmeredith@commerce.state.wi.us.
The Department of
Commerce Safety and Buildings Division is an equal opportunity service
provider and employer. If you need assistance to access services or
need
material in an alternate format, please contact us, 608-266-3151, TDD
call relay 711.
|