Fire Suppression and Fire Alarm Systems

Program Code Chapter: SPS 361-366

  • Disclaimer: Review WI statute for full program requirements


Overview

Reviews construction plans and provides inspections for public buildings, places of employment, and multi-family buildings for compliance with state statutes and building codes and sets standards for fire protection systems for fire suppression and fire alarm (FSFA) systems.

Plan Review

Plan review is required for commercial, industrial, and other public buildings 25,000 cubic feet or larger. Review is also needed for any size of school, high-hazard occupancy, and three-unit or larger residential building.

Plans are required for alarm, fire detection, and fire suppression ​​systems.

When submitted plans are compliant with the Wisconsin Commercial Building Code, you will be issued a conditional approval letter which gives you permission to start construction of the project, pending local permitting requirements.

Where do I submit my plans?

If the project is in a municipality with delegated authority to conduct plan review for buildings of that size, and the project does not involve a state-owned building or land, you may be able to submit to the municipality directly.

Use the FSFA Delegated Agent list to determine if your municipality has authority to perform plan review for your project.

If your municipality does not have the proper authority, submit your plans to DSPS via esla.wi.gov.

What is needed for plan review to DSPS?

  1. Owner information

  2. Designer/Supervising professional information

  3. Site location

  4. Building information

  5. Plan set (signed, sealed, and dated)

  6. SBD-8128, Checklist for Fire Suppression and Fire Alarm Plan Review

  7. SBD-8102, Statement of Special Inspections and Testing, as applicable

  8. Supporting documentation (for fire suppression):

    1. Hydraulic Calculations (signed, sealed, and dated)

    2. Material Product Data Sheets

    3. Worksheets, as applicable

    4. Copies of any previous correspondence with the Department regarding this application/project

    5. Other documents as directed in the checklist

  9. Supporting documentation (for fire alarm)

    1. Voltage Drop and/or Battery Calculations, as applicable

    2. Material Product Data Sheets

    3. Copies of any previous correspondence with the Department regarding this application/project

    4. Other documents as directed in the checklist

  10. Supporting documentation (for underground private fire service)

    1. Complete underground fire service main plans

    2. Thrust block calculations, as applicable

    3. Material Product Data Sheets

    4. Copies of any previous correspondence with the Department regarding this application/project

    5. Other documents as directed in the checklist

  11. Plan review fee payment.

See the FSFA guideline documents on the Reference Material page for more information.

See the eSLA Information page for user guides and general instructions. 

Permit

DSPS does not issue fire suppression or fire alarm permits. See the local municipality and/or local Fire Department covering your project location. However, note that a local permit is conditional on an approved plan review.

Inspection

Inspection of fire protection system construction and installation is required in accordance with the local building permit and plan review conditional approval letter.

Resources

Contact Us

If the municipality covering your project location has been delegated authority to inspect buildings of your size, and the project is not for a state-owned building or land, contact the municipality directly.

Use the Commercial Building and FSFA Inspection Delegated Agent List to determine if your municipality has authority to inspect your project.

If the municipality does not have proper authority, use the Inspector Look-Up Tool to determine the DSPS-appointed inspector for your county.

If the municipality covering your project location has been delegated authority to conduct plan review for buildings of your size, and the project is not for a state-owned building or land, contact the municipality directly.

Use the FSFA Plan Review Delegated Agent List to determine if your municipality has authority to review plans for your project.

If the municipality does not have proper authority, contact the DSPS plan review team at DspsSbFireProTech@wisconsin.gov. 

DSPS maintains program-specific email inboxes (tech boxes) to answer general code questions. Responses should not be construed as formal code interpretations nor do they supersede any previously issued correspondence from DSPS. Tech boxes should not be used for projects where code officials are already involved.

For general questions not related to specific programs or technical codes, use these contacts:

Subscribe to email updates from DSPS and receive upcoming announcements and notifications.

  1. Go to https://public.govdelivery.com/accounts/WIDSPS/subscriber/new

  2. Enter your email address and click Submit.

  3. Under Subscription Topics, expand the Industry Updates section.

  4. Check all the topics of interest to you.

  5. Scroll to the bottom and click Submit.

More Information

Related Pages

You may be interested in the pages below.

Codes and Statutes

Explore codes and statutes for DSPS public safety programs.

Credentialing

Find information on DSPS credentials related to this program.

Back to top button