Inspection Checklist For Typical One and Two Family Dwellings

Construction

320.09 (09)

Permit card posted

Zoning 321.33

Proper setbacks

Footing Inspection

Footings

321.16 48"

Frost depth including at basement walkouts

321.12 & 321.33

Proper planned sill elevation for zoning and drainage

321.14 (2)

Soil - no organics, uncompact fill, water, frost

321.16 & ACI 318 5.12

(shall be insulated if cold weather) and verify frost depth likely at site

321.17

Groundwater/clay: tiles with bleeders 8' o.c. (also requires 4" base course under slab and damp roofing of block foundations)

321.15

Forms or adequate soil stiffness (normally will form footings if tiles or basement floor base course required)

321.15 (2)

Form or trench sizes:

  • width: 8" plus foundation wall width

  • depth: 8" except fireplace and chimney footings to be 12"

  • columns: 12” x 24" x 24" (can include slab thickness)

  • footings for basement center bearing walls

320.10 & ACI 318 15.9.2

Rebar per plan or as needed to bridge problem spots

321.02 (3)(e)

Protected from freezing during cure

321.125

Silt fence, straw bales, or non-channel matting to protect downslope perimeter; 12" thick (3” to 6” diam. clean stone) tracking pad on all access drives (50 ft. length or to the foundation); soil stockpiles protected by proper erosion control methods; waterbodies and drainage ways protected from sediment discharge; no tracking onto street; off-site inlet protection; recheck as needed for repair and maintenance on future inspections.

Foundation Inspection

321.15 (2)(a)

Footing has minimum 4” each side of foundation wall and 8” minimum depth

321.18

Proper foundation thickness, pilaster spacing, and reinforcement per code tables

321.18 (3)

Maximum fill height for unreinforced HCB supporting WF: 8" block - (6 courses) in nongranular; 5' (8 courses) in granular; 10" block - 6' (8 courses) in nongranular; 6’ (9 courses) in granular

321.15 (2)(c)

Stepped foundation lintels or reinforcement (short steps okay with plain concrete)

321.18 (3)(b)

Rebar or other reinforcement per plan

321.26(3)

Type M or S mortar 321.26(12) 1/2" maximum mortar joint

321.18 (3)

Anchor bolt placement: minimum 6’ o.c. for concrete and 2 1/2' o.c. for HCB

321.26(9)

Beam to bear on: 8" height solid of solid concrete (or steel plate) 321.17 (3)(d) Required tiles: gravel bed of 2", cover of 12"

321.18 (3)

Block damp proofed in clay soil

322.32 (6)

Foundation insulation per energy worksheet including frost wall under basement walkouts

321.07 (2) & 322.34(3)(a)

1:1500 crawl space venting and 14" x 24" access

321.02 (3) and 321.26 (1)

Protected from freezing during cure

321.18 (1)(c) & (d)

Walls braced or floor system in prior to backfill

321.16, 321.12, 321.10

Proper elevation for frost depth, zoning, drainage, and protection of wood from decay

Fireplace

321.29(3)

See Heating Checklist

Basement Floor Inspection

321.17 (3)

Bleeders 8' o.c. with tar paper over interior joints

321.17, 321.20 (2)(3)

4" clean base course if clay soil or tiles required

382.36 (8)(a)2.

Storm crock lip to be 1" above floor

321.20

Minimum 3" concrete floor thickness

321.203 (1)(2)

Minimum 4" garage floors on 4" base course, Floor slopes to drain toward overhead door or to an interior floor drain that complies with SPS 382

321.16

Ground to be free of frost

Permanent Wood Foundation (PWF) Excavation Inspection

Permanent Wood Foundation Design Specification Manual

2007 Edition American Forest & Paper Association American Wood Council

ANSI/AF&PA PWF-2007

3.2

Design Properties of Soil

  • Determine .design properties of soil. Good to Medium Drainage, Poor Drainage, Poor to Unsatisfactory

2.5 4.1.2

Aggregate for Footings and Fill

  • Washed gravel, free of organics 4in. clear granular (3/16" - 3/4") Crushed Stone, washed with no more than 10% fines (material that passes a 3.16 in. sieve) Max size ¾ inch Sand, coarse min 1/16 in. free of organics, clayey or silty soils

4.1.4

Sump

  • Provide sump in soils classified as GW, GP, SW, SP, or GM Sump shall extend 24 in. below the top of granular drainage layer.

5.5.2

Composite Footings

  • Per design specifications prescribed in document Granular footing width 2 x footing plate width, and thickness 3/4 x footing plate width (2 x 8 or 2 x 10 typical [for 7' backfill]. If interior bearing wall, then same rules apply. [2" x 6" minimum footing plate])

5.5.1.1

Footing plate at least at frost depth; or if Group 1 soil or positively drained then bottom of granular fill

5.5.2 and 5.5.3

Column footings as for conventional construction or engineered wood and gravel, per design calculations prescribed in document

5.4.5.5.1

Anchorage of Foundation Wall and Footing

  • If concrete footer used, place on 4” granular that is positively drained or provide bleeders at 6‘ O.C. For basements: anchored to basement floor slab by spikes and designed per Chap. 11 NDS. For crawl spaces: anchored to concrete pad on each side by spikes and designed per Chap 11 NDS

1.3 and 2.3.3

All wood within 8" of grade treated to "FDN" standards and so stamped in accordance with AWPA U1. Treated field cuts in accordance with AWPA M4.

2.4.1 and 321.10 (5)

Fasteners and connectors used in preservative treated wood shall be Type 304 or 316 stainless steel, or hot dipped galvanized zinc coated steel fasteners where excepted.

5.5 and 5.5.2.1

Framing connections properly designed. (Critical)

5.5

Properly sized footing plate per design calculation set in the standard (2 x 8 or 2 x 10 for 7” backfill and 2 x 8 studs)

5.2.3 and 5.4.4

Design of Lateral Connections

  • Footing plate secured to wall plate (10d 12” O.C.) Design in accordance with the NDS

5.5

Provide support frame under stepped footing

5.4.1

Design of Studs

  • Properly sized studs Per design calculations in the standard (2” x 8” usually for 7” backfill)

5.4.3

Joints in footing plate and top plate staggered at least one stud space form joints in the corresponding plate

5.5.3

Adequate bearing stress (1 ½” – 2”) bottom of studs against floor slab

5.4.5.5

Studs secured to plates: Basement Wall anchorage to resist wind uplift (2 – 16d at bottom plate; 4 – 20d or U framing anchor at top plate)

5.2.3 and 5.4.3

Top plates secured together (10d face nailed 2" o.c.)

5.2.3 and 5.4.3

Joists secured to top plate (common joists with U framing anchor; header joist with 8d 8" o.c.; end joist with 8d 4" o.c.)

5.4

On end walls, provide full depth joist blocking (24" o.c. for 7' backfill) between top plate and parallel joist (secured with anchor or 8d 4" o.c. to top plate, 9 - 6d to floor sheathing)

5.4.2

Properly sized plywood sheathing (19/32" 40/20 for 12" o.c., 23/32" 48/24 for 16" o.c. and 7' backfill)

5.5.2

Properly secured plywood per spec. (8d 6” o.c. on edges, 12” o.c. 23/32” 48/24 for 16” o.c. in field)

5.2.3 and 5.4.3

Reinforce top plate with additional bolted top plates if stairwell opening is adjacent to foundation wall (4 additional plates for 10' opening)

4.1.7

If unequal backfill, provide shear strength (Between 2' and 6' differential, provide additional sheathing nailing of all walls and block and possibly double sheath end walls to act as shear walls. Also provide interior shear wall(s) if house is longer than 24')

2.6 and 4.1.5

Caulk plywood joints

2.7, 2.8, 4.1.3, 4.1.6, and 4.1.5

Six mil poly over below-grade foundation wall down to footing plate. Joints lapped 6" and caulked. Top edge caulked to wall and protected above grade with wood or similar material

4.1.7

  • Granular fill for 1/2 excavation height

  • Protect granular fill with proper erosion control BMPs

4.2.1

Insulation of exterior walls per UDC SPS 322

4.2.2

Vapor Barrier – with Vented Air Space

  • b/t insulation and plywood foundation wall, barrier shall be installed from the upper plate and extend down to the bottom plate

4.2.3

Vapor Barrier – with No Vented Air Space

  • Barrier shall be installed from the upper plate to approx. one foot below outside ground surface

321.07

Crawl Space Access per 321.07

4.2.2

Crawl Space Ventilation: per 322.34

4.1.4

Sump Requirements

Framing Inspection

General and Roofs

Suggested order of inspection:

  1. Scan exterior layout for offset walls, overhangs, wings and porches.

  2. Inspect in general order of exterior garage, upstairs, downstairs, basement.

  3. Follow load transfer down to earth including linear loads from bearing walls and any masonry and point loads from header ends, beam ends, and columns.

  4. Check for adequate fasteners especially for foam sheathed homes.

  5. For metal anchors, all holes generally filled with special connector nails (not roofing nails).

Roofs

321.28 (7)(d)

Cricket (saddle) if chimney over 30" wide

321.27 (9)

  • Roof sheathing

  • Properly sized: minimum thickness 5/8” for solid sheathing on rafter spacing of 24” or less, ¾” minimum thickness for spaced sheathing

321.08 (2)

Tenant separation in attic

321.27 (1)

Roof openings headered similar to floor openings (around skylights, chimneys, etc.)

321.02 (1)(d)

Roof member to top plate: 2-16d or 3-8d

Rafters

2 x sawn members

321.27 (4)(b)

Ridge board to be 2 x if rafter pairs offset; ridge board shall have a depth at least equal to the length of the cut end of the rafter abutting it

 321.27 (4)(a)

Collar ties every third pair in upper one third

321.27 (6)

  • Hip rafters 2" deeper than commons

  • Interior end of lower intersecting ridge board supported

321.27 (6)(a)

Valley rafters doubled and minimum 2" deeper than commons

321.28 (2)

Large cathedral ceilings and 1 1/2-story homes with properly sized ridge beam; or cantilevered wall ties; or rigid ridge connection (batts or gussets) and wall ties, or other means. Adequate hangers or bearing of rafters on ridge beam.

321.27 (8)(b)

  • Notches maximum 1/6 of depth and not in mid-1/3 span

  • Notches in end maximum 1/4 depth of rafter Holes in center of rafter and maximum 1/3 depth of rafter

321.22 (4)(b)

Minimum bearing of 1 1/2" on wood, 3" on masonry or anchor clips (ledger boards for shed roofs well anchored)

321.27 (4)(e)

Gable end ladders anchored to interior rafter if overhang more than about 1'

Rafters

Wood I Member Rafters (TJIs, etal.)

Per Manufacturer.

General

  • Properly sized

  • No cutting of flanges or other damage

  • Proper cutting of web - watch holes by bearing points

Ridge

  • Must be supported by ledger board or ridge beam, not ridge board and collar ties

  • Bottom flange bearing condition

    • blocking or X-bracing between I members

    • beveled top edge of ridge beam

    • pairs of members gusseted with 3/4" plywood or lapped with filler block between members

  • Framed into ridge beam or ledger condition

    • proper hangers - may need web stiffeners

    • strap together I members across ridge if more than 7/12 slope

Eaves

  • Uncut bottom flange must bear on beveled top plate (or hanger if < 6/12 slope)

  • Cut bottom joist flange must bear fully on top plate and have web stiffener(s) or cripples

  • Blocking or X-bracing between I members

  • Refer to manufacturer's literature for other eave details

Ladders

Outriggers notched to top chord

321.27 (8)

  • Roof trusses

    • proper factory fabrication per plans

    • no modifications or damage

    • Bearing

      • end bearing points under scarf cut, factory blocking or cantilever strut

      • any interior bearing points to be at panel points

      • adequate bearing width for design (typical 3 1/2" for dwellings) (need extended seat or "double shear" hangers)

    •  Girder trusses

      • laminated girder trusses properly nailed together (typical staggered o.c. spacing: 10" Top Chord, 3" Bottom Chord, 4" webs)

      • proper girder truss hangers for common trusses

      • adequate end columns or multiple studs for girder trusses

    • Permanent bracing per plans or markings

      • Location

      • TConly if no rigid sheathing

      • BC - 10' o.c. only if no rigid ceiling such as drywall

      • webs - typically for webs over 8' long or if intersecting interior bearing point

      • cantilever struts at mid-point

      • TC of bottom portion of piggyback type truss

    • Method of lateral bracing

      • near panel points on TC and BC

      • minimum 1" x 4" continuous or lapped for one truss bay

      • anchored into solid (not frame) end walls or diagonally braced in plane of brace (up or out at end walls)

    • Gable ends fully supported along full length unless trussed

Ceilings

321.06

Ceiling height, at least 7 feet, habitable rooms may be less than 7 ft. if at least 50% of the room’s floor area has a ceiling height of at least 7 feet. Beams and girders shall not project more than 8 inches below the required ceiling height.

321.07 (1)

14" x 24" scuttle opening for attic access

321.27 (2)

Properly sized ceiling joists

321.27(5)

  • Joist to rafter: 3-16d

  • Joist to plate: 2-16d or 3-8d

  • or in accordance with the floor joist requirements under s. SPS 321.22(4)(a)1.d.

Frame Walls

321.25 (2)

  • Top plate

    • doubled or bearing members above studs (includes basement center walls)

    • lower top plate broken over stud

    • corners and tees tied by laps or straps

  • Proper stud sizing and spacing (2 x 6 16" o.c. or 2 x 4 12" o.c.)

321.25 (8)

Wall Bracing

321.25 (8)

  • Wall brace plans meet code requirements

  • Redesign / reconfigure wall bracing detail on plans as needed to satisfy code requirements

(8)(b)

Wall bracing methods match those on plans

(8)(b)

Proper products used for wall bracing

(8)(b)

Nailing patterns as per code

(8)(c)

Brace panels installed to proper lengths

(3)(a), (b)

  • Headers where load bearing

  • properly sized

    • Headers > 3’ but < 6’ in length shall be directly supported on each end by the single common stud and 1 shoulder stud

    • 3 feet or less, supported by single 2 x 4 common stud and a shoulder stud; or single common stud with a framing anchor attached

    • Headers greater than 6’ in length shall be supported on each end by the single 2 x 4 common stud and 2 shoulder studs

321.18(1)(c)3.

Bottom plate anchored in garage and whole foundation

321.10 (2)

Treated Wood Required

(a)

All wood resting directly upon or embedded in earth

(c)

Joists within 18 inches above exterior grade unless protected with a moisture barrier

(d)

Girders spanning directly over and within 12 inches of earth

(e)

Sills and rim joists resting on concrete or masonry and also below grade or within 8 inches above final exterior grade

(f)

Siding and sheathing in contact with concrete, masonry, or earth and within 6 inches above final exterior grade

(g)

Ends of wood structural members and their shims resting on or supported in masonry or concrete walls and having clearances of less than ½ inch on the top, sides, and ends

(h)

Bottom plates or sole plates of walls that rest on concrete or masonry and that are below exterior grade or less than 8 inches above final exterior grade

(i)

Columns in direct contact with concrete or masonry unless supported by a structural pedestal or plinth block at least one inch above the floor

(5)

Proper fasteners compatible with treated lumber

321.25 (4)

Reinforce stud if more than 1/3 depth bored or cut out

321.085 (1)(2)

Fire blocking at soffits, dropped ceilings, openings around wires, cables, vents, pipes, ducts, chimneys, etc., concealed spaces, connections between concealed vertical or horizontal spaces

321.08 (1)

Fire Separation per code specifications

(a)

Attached garages

¾ hour fire-resistive construction or shall be:

  • One layer of 5/8 inch Type X gypsum drywall on the garage side of the separation wall or ceiling

  • One layer ½ inch gypsum drywall on each side of the separation wall or ceiling

  • Two layers of ½ inch gypsum drywall shall be used on the garage side of separation wall or ceiling

  • Drywall joints taped and sealed

  • Gap between joints no greater than 1/20 inch, joints backed by solid wood or another layer of drywall

(b)

Structural elements exposed in an attached garage shall be protected as per 321.08 (a)

(c)

Doors: minimum fire resistant rating of 20 min.

(2)

Dwelling Unit Separation per code specifications

(a)

Dwelling units separated from each other: attics, basements, garages, vestibules and corridors

(b) (d) (c) (e) (f)

  • Attic Separation: complete separation extended to underside of the roof deck,

  • Walls: At least one layer 5/8 inch Type X gypsum wallboard or equiv. Or two layers of ½ inch gypsum wallboard or equiv.

  • Doors: Minimum 20 minute fire rating

  • Floors and Ceiling: 5/8 inch Type X gypsum wallboard with joints in compliance with sub. (1) (a)2.

  • Building Design - recheck architectural plan review

321.04(2)

  • Stairs

    • 36 inches minimum width

    • Handrails and trim may project max. 4.5 inches into width area at each side

    • 6'4" headroom measured from the stair’s nosing to the ceiling, soffit or any overhead obstruction

    • 8" riser, 9" tread

    • winders in series - minimum 7" tread 12 inches in from pivot (individual winder - equal to tread depth of the rectangular steps 12 inches in from pivot)

  • Handrail: located at least 30 inches, but no more than 38 inches above tread nosing

(3)

  • Handrails: required on stair flights with more than 3 risers. At least one handrail provided for full length of stair flight.

  • Handrails: symmetrical about the vertical centerline to allow for equal wraparound of thumb and finger

  • Round or truncated round handrail: max. whole diameter of 2 inches

  •  Rectangular handrails: max perimeter of 61/4 inches with a max. cross sectional area of 27/8 inches.

(4) (a)

Landings: Intermediate landing required for any stairway with a height of 12 feet or more

(b)

  • Landing: Provide a level landing at the top and base of every set of stairs. Landing as wide as stairs and measure at least 3 feet in direction of travel.

  • Doors at landings: Level landing provided on each side of any door located at the top or base of stairs

  • Exterior landing: Landing, platform or sidewalk located max 8 inches below the interior floor elevation. Minimum 36 inch length to in the direction of travel out of the building.

Brick Veneer Walls

321.26(7)(a) 1.

  • Brick ledge or base flashing provided

  • Maximum 1" corbel over foundation

(a)2.

Provide (1") air space behind brick

4.

Provide weep holes at max. intervals of 2 feet.

T.321.26 - C

  • Properly sized lintels

  • Large stone securely anchored with 1/4" dowels

321.26(8)(a)1

Proper flashing installed to drain water away from structural members

Floors

321.22(8)

Properly sized sheathing, as per Table 321.22-B

Joists

2 x sawn members

321.22(1)

Properly sized

321.10(1)

Untreated crawlspace joists at least 18" to earth

321.22(4)

Bearing - minimum 1 1/2" on wood, 3" on masonry

321.22 (1) (c)

Where a sill plate is provided for floor joists on solid block top course masonry, the sill plate shall be fastened to the foundation.

321.22(1)(d)

Where the masonry wall has an open top course, a sill plate at least as wide as the foundation wall shall be fastened to the foundation.

 321.22(4)(c)

The tail end of a floor joist may not extend past the edge of a beam by more than the depth of the floor joist.

321.22 (5)

Notching and boring - notches maximum of 1/6 of depth and not in mid-1/3 span - notches in end maximum 1/4 depth of joist - holes in center of joist and maximum 1/3 depth

321.22 (6)

Overhangs

  • maximum 2' where common joists are extended over wall and carry roof load

  • lookout joists anchored to doubled common joist setback

  • 2 x overhang

Joists

Wood I member Joists (TJIs, etal.) Per Manufacturer.

General

  • Properly sized

  • No cutting of flanges or other damage

  • Proper cutting of web - watch holes by bearing points

Rim

  • 1 story: 3/4" plywood

  • Carrying 2 stories: I-blocking: 2 layers 3/4" plywood; pair of 2 x 4 cripples; or continuous 2 x rim

  • Provide solid blocking under point column loads

Center bearing

  • I-blocking or 2 x 4 cripples if bearing wall above

  • May need web stiffener

Sistered 2 x cantilevered deck

  • Plywood filler between I-member and 2 x joist

  • Maximum 4' cantilever

Cantilevered I-member with roof load

May need to reinforce I-member

Hangers

  • Proper nails and nailing

  • Sized for I-member thickness and either full depth or install web stiffener

  • Top mounted hangers on I-member header - may also need backer block

  • Filler between doubled I-member header at hangers

321.22 (2)

Parallel Chord Floor Trusses

  • no modifications or damage

  • bottom bearing trusses not flipped top for bottom

  • top bearing trusses bearing within 1" of last web

  • strong back installed 10' o.c. and tied to end walls

  • any interior bearing point at joint

  • no cantilevers unless engineered

  • if top bearing trusses used on frame wall, will need fire stopping in wall at bottom chord

321.22 (7)

Floor openings (around stairs, fireplaces, chimneys, plumbing, etc.)

  • doubled trimmers and headers if header over 4'

  • hangers or bearing for headers over 6'

  • clips, hangers, blocking plates, or bearing for tail joists over 8' including joists over basement windows

Beams

321.22 (3)

Properly sized

321.22 (5)

No notching or boring

T. 321.22 A-2

Built up wood beams to have double row of 10d nails spaced 18" in each row; member joints within 1/4 span points, no adjacent butt joints, maximum 1/2 of plies jointed at same 1/4 point (especially critical for side-loaded beams)

321.02

Proper beam nailers (width equal to beam width)

321.22 (3)(a)

Adjoining ends to be fastened together at columns

321.22 (4)

Bearing length of 3" on 8" thick solid masonry concrete or on metal

321.02

Adequate beam columns

321.15 (1)(b)

Beam columns on footings

321.10 (1)

Foundation

321.18 (1) (a)(b)(c)

Lateral support for tops of masonry wall including knee walls

  • foundation bolts or anchors

  • ledger board and end wall blocking

  • furred interior wall with connection to floor joists

Insulation Inspection

322 20 – 322.39

Envelope (ceiling, walls, floors, foundation) insulated per Subchapter IV SPS 322 and ResCheck/RemRate Heat Loss Programs or SPS 322.31 Prescriptive tables:

Insulation matches inputs used for heat loss calcs and cross section plans

322.20 – 322.39

Check installation and plans of window U values and insulation R values for consistency with inputs used in heat loss calculation

322.20 (6)

A permanent certificate from the heat loss calculations shall be posted on or immediately adjacent to the electrical distribution panel. Include predominant R-Values and U-Values

322.20 (5)

Thermal Resistance Identification shown on insulation greater than 12 inches wide

322.20 (5)

Blown attic insulation: ID tag per 300ft2 tag min 1 in height

Text facing attic access

322.20 (4)

Manufacturer’s installation instructions available at job site

322.37 Joint and Penetration Sealing

 behind studs at wall corners and intersections

322.37 (3)

attic knee walls

322.37 (3)

gable ends of cathedral ceilings

322.37 (3)

bay window seats and roof/ceilings

322.37 (3)

skylight wells

322.37 (3)

Recessed lighting fixtures

322.37 (3)

between window/door jambs and framing

322.37 (3)

Between wall assemblies, sill plates and foundation

322.37 (3)

Penetrations of utility services through walls, floor and roof assemblies, top and bottom roof plates

322.37 (3)

Attic and crawl space panels

322.37 (4)

Recessed lights

322.37

Fan housings

322.34

spaces over unheated areas such as garages and crawlspaces

322.32(7)

second floor box sill

322.32 (8)

Overhang Joist Spaces

322.32(9)

2nd story walls adjacent to attics

322.30 (4)

  • house/garage wall (including insulating sheathing)

  • window glazing

322.21

support provided for ceiling insulation where not dry walled (stairwells, chases, etc.)

322.42(1)

All heating (supply and return) ducts exposed to unheated spaces insulated to R-8 including in exterior walls

382.40(8)(a)

Water piping protected from freezing by insulation in exterior walls

322.38(1)

Continuous vapor barrier on warm side of all insulation

  • seams lapped at least 6 inches or batt flanges stapled to stud/joist faces

  • tightly cut around penetrations

  •  interior soffits properly handled

  • vapor barrier paint also okay

322.37 (3) (4)

Top plate penetrations sealed

321.37 (5)

Exhaust fans terminate outside dwelling

322.39(1)

Attic venting: one side 1:150, high/low 1:300; insulated roof vents = 1/3 square foot, air chutes in or raised truss heel

322.37(3)

Sill sealer on foundation

322.34

  • Vapor retarder properly covering soil in Crawl Spaces

  • Insulated Crawl Space per Table 322.31-1

323.08(2)

Metallic duct for kitchen hoods

Insulation of Permanent Wood Foundation

Permanent Wood Foundation Design Specification Manual 2007 Edition

American Forest & Paper Association American Wood Council

ANSI/AF&PA PWF-2007

322.31

 Insulated per Energy Worksheet or an acceptable software program

322.38(1)(b)

Continuous vapor barrier

Below-Grade per PWF Manual

Permanent Wood Foundation Design Specification Manual 2007 Edition

ANSI/AF&PA PWF-2007

6.10.3.

Provide air space between insulation and foundation sheathing or

6.10.2.

Stop vapor barrier 1' below outside grade and fold against foundation sheathing

6.10.4.

Stop insulation 2" above bottom plate

Construction Final Inspection

Outside

Zoning

Broken sidewalk and curb replaced

321.12

Grade away from dwelling

321.125

Final erosion control measures in place or site “stabilized” per code

322.31 Table 322.31-1

Foundation insulation protection

321.24(2)(c)

Caulking or flashing of penetrations and joints

321.24 (4)

Weather resistant wall covering (painted if necessary)

321.24(3)(4)

Horizontal plywood siding joints lapped, Z-flashed, or battered per mfr. and APA

321.10

Untreated wood clearance to grade

321.27(4)

Proper roof flashing

Various

Code complying decks

323.02 (3)

Bath exhaust terminating outside dwelling

321.04(2)

Code complying steps, riser heights , tread depths

321.26(7)

Brick veneer installed properly

Inside

321.09

Smoke detector in each sleeping room, outside of each sleeping room within 21 feet of sleeping room door opening (at centerline) On floor levels without sleeping rooms, one alarm on each level

(2)

Smoke Alarms hardwired per code

321.097

Carbon Monoxide (CO) detector installed on each floor hardwired per code

322.37(3)

Minimum 14" x 24" weather-stripped scuttle to each attic

321.08(1)

Garage fire separation in place including door casing, eaves, complying attic scuttle, and protection of beams and columns supporting living space above

321.05(3)

Safety glazing in doors and sidelights

321.04

Code complying stairs - risers, tread, handrail, headroom, guardrail

321.03

Code complying bedroom egress windows in basement and second floor if no second exit

Basement

321.22 (3)

Columns secured to beams, providing full beam width bearing

321.25 (6)

Anchored to floor

321.09

Smoke detector / CO detector

321.097

Carbon Monoxide (CO) detector installed hardwired per code

321.085

Fire stop around all chimneys, vents, ducts, and pipes in ceiling and also open stud spaces in split level

322.32 (7)

Box sill insulation

322.34 (2) (1)

Vapor barrier on crawl space floors, organics removed

321.22(5)

Recheck notching and boring of joists

321.22(1)

Recheck floor joist support and header

Heating

Rough Heating Inspection

323.11(1)

Metal Chimney/Vent Listing

323.11 (2)

Proper roof termination - 3' above roof and 2' above roof within 10' (B vent with listed cap can terminate 1' above a roof with slope less than 8/12) Listing

321.08

Fire stop and clearance to combustibles per label

321.08 (2)

Proper Dwelling Unit Separation: attics, doors, walls, floors and ceilings at roof, ceiling and floor penetrations and at each floor level unless in a chase

Listing

Insulation shield in attic

Listing

Enclosed in chase through occupied spaces

Rough ductwork (and-to-be concealed ducts) 323.09(2)(b)

At least one return air opening per floor

321.22(5)

Proper notching and boring of joists - maximum notch of 1/6 of depth but not in mid-1/3 span

321.22(5)

Proper notching of studs - maximum 1/3 depth or reinforce

T.323.08-A

Minimum 30 gauge for concealed ducts

323.08 (1)

Not used for any other systems (any electrical, telephone or CATV boxes in return air spaces to be separated off)

T.323.08-B

Supported 10' - 12' o.c.

323.08(8)

Joints securely fastened

323.08(2)

Ducts serving kitchen hoods to be metallic

321.32

Factory-built fireplace

323.18(1)

  • Equipment Installed per listing and manual (which is to be left on site)

  • Safety strip in front of opening

  • Chimney installed per above

Listing

No combustibles below top spacers or closer to jacket than listing (1" typical)

323.09

No combustion air from garage without backdraft damper

Listing

Manufactured Fireplace

  • Safety strip installed

  • Clearances to combustibles

Rough Masonry Fireplace and Masonry Chimney

Masonry Fireplace

321.15(2) (d)

Supported on 12" thick footings that extend 4" on either side

321.29

Fireplace supported on minimum 8" thick foundation

(10)

Cleanout provided

(6)

Properly sized hearth extension: less than 6 square feet opening - 8" to sides, 16" to front; bigger - 12" to sides, 20" to front

(3)

Side and back walls of fireplace at least 8" thick

Masonry fireboxes of firebrick laid in thin refractory cement

(1)

Flue sized for fireplaces: round: 1/12 of opening; rectangular: 1/10; minimum 75 square inches

Masonry Chimney

321.30(2)

Proper flue size for other appliances

(3)

Multiple flues separated by 4" masonry

(9)(a)

Minimum clearance to combustible framing of 2" for interior chimneys and 1/2" for exterior chimneys

(9)(b)

Minimum clearance of 1/2" to combustible trim

(9)(c)

Draft stop at each floor level

(8)

Minimum 2" chimney cap

321.29(2)

Terminate 3' above roof and 2' above any roof within 10'

Heating Final Inspection

Outside

NFPA 54 7.2.1

Gas pipe entrance nipple protected - galvanized, epoxy coated, taped or sleeved

323.11

Sidewall appliance venting

Typical Listing per NFPA 54 12.7.2

3' from gas meter or regulator

12.7.2

1' above grade

3.3.107

Sealed combustion

10.7.1.2

  • 50,000 BTU or less - 9" from building opening

  • Over 50,000 BTU - 12" from opening

10.7.2

Power vented - 4' from openings

323.11 (2)

Chimney and vent termination - 3' above roof and 2' above roof within 10'

323.13 Typical Listing

B vent with listed cap can terminate 1' above roof with slope less than 8/12

323.16 (1)/NFPA 58

LP Tanks

6.3

125 gallon tank - 5' from doors or windows, 10' from any sources of ignition (AC, furnace intakes)

6.3

125-1200 gallons - 10' from building, sources of ignition or property line

323.16 (1)(c)

On adequate supports

6.3

Safe from vehicle damage

6.3

Gas regulator outlet to be 3' horizontally away from building opening below outlet

6.8.1

Piping and regulator properly secured

Inside

323.09 (1)&(2) T-323.07

Dampers, registers, and grilles

Listing

Insulation shield around vent or chimney in attic

323.16/NFPA 54 9.6.4

Gas range and dryer shutoffs within 6' of appliance

Woodstoves properly installed (see checklist)

323.045

Fireplaces

321.29 (6)

Hearth extension properly sized, less than 6 square feet: 8" to sides, 16" to front; bigger: 12" and 20"

321.32 (1)(a)

Factory-built fireplace firebox caulked or mortared to surround

321.29 (11)

Proper mantel and trim clearances; masonry fireplace: not within 6", maximum 1/8 projection per inch of clearance between 6" and 12" away from fireplace opening

Basement

NFPA 54/7.2.6

Gas pipe hangers: 1/2": 6' o.c., 3/4" and 1": 8' o.c. lines on 8' centers

321.30 (9)

2" clearance between chimney and combustibles

323.11 (1)

Proper clearance to B vent (typically 1")

Listing

Furnace and water heater properly installed (see heating checklist)

Ducts

323.09(1)

Shutoff dampers on accessible runs

322.17

T.323.08-B

Supported 10' - 12' o.c.

323.08(1)

Not used as chases for other mechanical systems

General Heating Plant

323.04

To be installed per listing

323.18(1)

Manual left at site

322.15

Sized per ResCheck/RemRate Energy Worksheet

323.17(2)

24" of clearance in front of portions needing servicing

322.31 (3) and T-322.31-3

80% AFUE minimum

322.39 (5)

Automatic flue damper (or outside combustion air or induced draft or secondary exchanger) and electronic ignition

Typical Listing

If damp floor, provide raised base

NFPA 54

Gas Piping

9.6.4.1

Shutoff valve within 6'

7.6.1

Drip tee

NEC 90

HVAC Electrical Connection - Venting

Dedicated circuit (new construction)

4450.53

Properly fused per data plate

440.14

Disconnect within sight

440.61

Grounding connection made

323.06

Combustion air

(1)(a)

100 cubic feet of room volume per 1000 BTU (12.5 square foot floor area if 8' tall) input or bring in air

(4)(d)4.c.

House air - two openings (high/low), each 1 square inch per 1000 BTU (figure 20% free air for wood louvers and 60% for metal louvers)

(4)(b)

Outside air - two openings (high/low) each 1 square inch per 4000 BTU

Venting

Atmospheric Venting

T.323.15-C

6" min. clearance between single wall connector and combustibles

323.045 (4)(d) 4.

Connector securely joined and supported

323.155

  • Vent sized to appliance collar

  • Co-venting - no exhaust pipe tees or back-to-back flue entrances – f

  • Venting area shall be at least equal to the size of the largest vent connectors plus at least 50% of the area of the other vent connectors.

323.11(1) + (2)

  • Termination - 3' above roof and 2' above roof within 10' (B vent with listed cap can terminate 1' above roof with slope less than 8/12)

  • Sidewall venting (typical)

Listing

All vents under positive pressure to be tightly sealed Listing PVC vent supported 3' o.c.

Listing

PVC vent sloped 1/4" per foot to furnace

Listing

Maximum vent length per manufacturer (typical 30-40 feet plus two elbows)

NFPA 54 and Listing

Termination

12.7.2

3'from gas meter or regulator

12.7.2

1' above grade

12.7.2

Away from damageable items (AC, electrical equipment)

3.3.107

Sealed combustion

12.7.2

  • 50,000 BTU or less

  • 9" from windows, etc.

12.7.2

  • Power vented

  •  4' from openings

Listing

Condensate drain vent in place

323.156

Condensate drain to sanitary drain

Ducts

T.323.08-A

Duct construction - Minimum Sheet Metal Gauge

323.08(1)

Not used as chases for other mechanical systems

323.09(1)

Duct dampers (on accessible ducts)

T.323.08-B

Rigid Duct Support 12' o.c.

323.08(8)

Joints securely fastened

323.09(2)(b)

No return air openings in same room as atmospheric vented appliance

323.09(2)(b)

Doors undercut if no return air opening in room

Boilers

T-(382.43-1)

Backflow prevention: per Table 382.43-1

Listing

Pressure/temperature blow off valve and pipe

Listing

Barometric damper in same room as appliance

Water Heater

323.04

Installed per listing

323.18 (1)

Manual left at site

323.17 (2)

Twenty-four inches clearance in front of portions needing servicing

382.40 (5)(d)

Pressure/temperature blow off valve and pipe discharging within 6 inches of the floor or receptor but not less than 2 x pipe dia. to floor

323.06

Combustion air - see furnace section

NFPA 54 5.5.6

Gas sediment trap

NFPA 54 5.5.4

Gas shutoff within 6 feet

T-323.15-C

Six inches clearance to smoke pipe

323.045 (4)(d)4.

Smoke pipe sections securely joined and supported

Listing and NFPA 54

Sidewall venting - see furnace section

Wood Appliances

323.045 (1)

To be listed and installed per listing

Listing

Proper clearances to combustibles

323.045 (5)

  • Proper floor protection

  • Supplemental units (connected to furnace)

323.045(8)

Connected on warm air side of furnace (stove not to dump hot air into furnace return air cabinet)

323.045(8)(e)

Three feet separation between stove and furnace

Chimney Connector

323.045(4)(b)

Eighteen inches clearance between single wall connector and unprotected combustibles

323.045(4)(c)

Readily accessible

323.045(4)(d) 4.

Sections joined with 3 screws or rivets

323.045(4)(d) 5.

Sections joined so creosote flows to stove

323.045(4)(d) 4.

  • Securely supported

  • Damper installed

Chimney

323.045(3)(b)

Vented to own flue

323.045(3)(a) 2

Lined masonry

323.045(3)(a) 1.

Factory built chimney to be 2100 Fahrenheit. high temperature (HT) type

Ducts

323.045 (9)

Supply duct clearances to combustibles

T- 323.045-F

  • First 3 feet from stove: 18 inches

  • 3 to 6 feet: 6 inches

  • Over 6 feet: 1 inch

Final Inspection Guidelines

The following items are generally critical items that must be complying in order for occupancy to take place:

  • All easily accessible electrical boxes closed up

  • Bathroom and kitchen plumbing fixtures in place

  • Smoke detectors

  • Guardrails

  • Steps and handrails

  • Erosion Control measures to be maintained by owner until site is stabilized (70% perennial vegetative cover)

The following items may generally be noted as non-complying on the occupancy permit and not require re-inspection

  • Caulking

  •  Final Grade

Return to UDC Program Page